Parameter

Setting value / Description / Note

Device

Parameter
type

P741

[-01]

...
[-23]

PZD bus out

(Process data bus out)

SK 540E

and above

S

[-01 ] = Status word

Status word, source from
P509.

[-02]

= Actual value 1 (P543 [-01])

[-03]

= Actual value 2 (P543 [-02])

[-04]

= Actual value 3 (P543 [-03])

[-05]

= Actual value 4 (P543 [-04])

[-06]

= Actual value 5 (P543 [-05])

[-07] =

Bus I/O Out Bit (P481)

The displayed value depicts
all Bus Out Bit sources
linked with or.

[-08]

= Parameter data Out 1

[-09]

= Parameter data Out 2

[-10] =

Parameter data Out 3

[-11] =

Parameter data Out 4

[-12] =

Parameter data Out 5

Data during parameter
transfer.

0000 ... FFFF (hex) This parameter provides

information about the
actual status word and
the actual values that are
transferred via the bus
systems.

[-13] =

Actual value 1 master function

[-14] =

Actual value 2 master function

[-15] =

Actual value 3 master function

[-16] =

Actual value 4 master function

[-17] =

Actual value 5 master function

Actual value of master
function 502/P503.

[-18]

= PLC status word

Status word via PLC

[-19]

= Actual value 1 PLC

[-20]

= Actual value 2 PLC

[-21]

= Actual value 3 PLC

[-22]

= Actual value 4 PLC

[-23]

= Actual value 5 PLC

Actual value data via PLC

P745

Option version

(Module version)

SK 5xxE

0.0 ... 999.9

Version status (software version) of the technology unit (SK TU3-xxx), but only when own
processor is present, therefore not for SK TU3-CTR.

Have this data available if you have a technical query.

P746

Option status

(Module status)

SK 5xxE

S

0000 ... FFFF (hex)

Actual status (readiness, error, communication) of the technology unit (SK TU3-xxx), but only
when own processor is present, therefore not for SK TU3-CTR.

Example:

0603

hex

High byte = 06

hex

=> Profibus

Low byte = 03

hex

=> Module ready + connection to master

Code details can be found in the respective BUS module manual. Different contents are shown
depending on the modules.

NOTE

When activated, the functions block current, quick stop, remote control and cancel error
are available at the (local) control terminals. To operate the drive, a high signal must be
present on the digital inputs being used before the drive can be enabled.