4 communication 4.1 process data, Process data structure – NORD Drivesystems BU0590 User Manual
Page 17
4 Communication
BU 0590 GB-0312
Subject to technical amendments
17
4 Communication
4.1 Process data
Control words and setpoints are transferred from the bus master / controller to the SK TU3-…bus module as
process data and in return, the status word and actual values are sent to the bus master / controller from the
FI. Transfer is carried out cyclically. The bus master / controller can access these process values directly, as
they are stored in the I/O area.
The length and structure of the process data is specified via the PPO types during the planning of the
PROFINET network.
The allocation of the values transferred in the setpoint/actual value area of the FI is made via the
parameters P543 to P548 or P543 [-01]…[-05].
4.1.1
Process data structure
The structure of the process data is defined by the PPO type.
4.1.1.1
Pure process data communication
Direction of
transmission
Transmitted data
( 4 Byte )
1st
word
2nd
word
... to SK TU3
Control word
Setpoint 1
... from the SK TU3
Status word
Actual value 1
Table 9: PPO 3
Direction of
transmission
Transmitted data
( 8 Byte )
1st word
2nd word
3rd word
4th word
... to SK TU3
Control word
Setpoint 1
Setpoint 2
Setpoint 3
... from the SK TU3
Status word
Actual value 1 Actual value 2 Actual value 3
Table 10: PPO 4
Direction of
transmission
Transmitted data
( 12 Byte )
1st word
2nd word
3rd word
4th word
5th word
6th word
... to SK TU3
Control word
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Setpoint 5
... from the SK TU3
Status word
Actual value 1 Actual value 2 Actual value 3 Actual value 4 Actual value 5
Table 11: PPO 6