NORD Drivesystems BU0590 User Manual

Page 18

background image

PROFINET bus module for NORD frequency inverters SK 5xxE

18

Subject to technical amendments

BU 0590 GB-0312

4.1.1.2

Process and parameter data communication

The exchange of process and parameter data is possible by selecting the PPO types 1 or 2.

Direction of

transmission

Transmitted data

( 12 Byte )

1st word

2nd word

3rd word

4th word

5th word

6th word

... to SK TU3

Parameter
number and
order label

Parameter
index

Parameter
value HI

Parameter
value LO

Control word

Setpoint 1

... from the SK TU3

Parameter
number and
order label

Parameter
index

Parameter
value HI

Parameter
value LO

Status word

Actual value 1

Table 12: PPO 1

Direction of

transmission

Transmitted data

( 16 Byte )

1st word

2nd word

3rd word

4th word

... to SK TU3

Parameter number and
order label

Parameter index

Parameter value HI

Parameter value LO

... from the SK TU3

Parameter number and
order label

Parameter index

Parameter value HI

Parameter value LO

Direction of

transmission

Transmitted data

( 16 Byte )

5th word

6th word

7th word

8th word

... to SK TU3

Control word

Setpoint 1

Setpoint 2

Setpoint 3

... from the SK TU3

Status word

Actual value 1

Actual value 2

Actual value 3

Table 13: PPO 2