PROFINET bus module for NORD frequency inverters SK 5xxE
42
Subject to technical amendments
BU 0590 GB-0312
Parameter
Setting value / Description / Note
Device
Parameter
type
P740
[-01]
...
[-23]
PZD bus in
(Process data bus in)
SK 540E
and above
S
[-01]
= Control word
Control word, source from
P509.
[-02]
= Actual bus value 1
[-03]
= Actual bus value 2
[-04] =
Setpoint 3
[-05] =
Setpoint 4
[-06] =
Setpoint 5
Setpoint data from main
setpoint (P510 [-01]).
[-07] =
Bus I/O In Bits (P480)
The displayed value depicts
all Bus In Bit sources linked
with or.
[-08]
= Parameter data In 1
[-09]
= Parameter data In 2
[-10]
= Parameter data In 3
[-11]
= Parameter data In 4
[-12]
= Parameter data In 5
Data during parameter
transfer: Order label (AK),
Parameter number (PNU),
Index (IND), Parameter
value (PWE 1/2)
0000 ... FFFF (hex) This parameter informs
about the actual control
word and the setpoints
that are transferred via
the bus systems.
For display, a BUS
system must be selected
in P509
[-13]
= Setpoint 1
[-14]
= Setpoint 2
[-15]
= Setpoint 3
[-16]
= Setpoint 4
[-17]
= Setpoint 5
Setpoint data from the
master function value
(Broadcast), if P509 = 9/10
(P510 [-02])
[-18]
= PLC control word
Control word, source PLC
[-19]
= Setpoint 1
[-20]
= Setpoint 2
[-21]
= Setpoint 3
[-22]
= Setpoint 4
[-23]
= Setpoint 5
Setpoint data from the PLC.
P741
[-01]
...
[-13]
PZD bus out
(Process data bus out)
up to
SK 535E
S
… [-01 ] = Status word
Status word, source from
P509.
[-02]
= Actual value 1 (P543)
[-03]
= Actual value 2 (P544)
[-04]
= Actual value 3 (P545)
[-05] =
Bus I/O Out Bit (P481)
The displayed value depicts
all Bus Out Bit sources
linked with or.
[-06 ]
= Parameter data Out 1
[-07 ]
= Parameter data Out 2
[-08]
= Parameter data Out 3
[-09]
= Parameter data Out 4
[-10] =
Parameter data Out 5
Data during parameter
transfer.
0000 ... FFFF (hex) This parameter provides
information about the
actual status word and
the actual values that are
transferred via the bus
systems.
[-11] =
Actual value 1 master function
[-12] =
Actual value 2 master function
[-13] =
Actual value 3 master function
Actual value of master
function 502/P503.