PROFINET bus module for NORD frequency inverters SK 5xxE

42

Subject to technical amendments

BU 0590 GB-0312

Parameter

Setting value / Description / Note

Device

Parameter
type

P740

[-01]

...
[-23]

PZD bus in

(Process data bus in)

SK 540E

and above

S

[-01]

= Control word

Control word, source from
P509.

[-02]

= Actual bus value 1

[-03]

= Actual bus value 2

[-04] =

Setpoint 3

[-05] =

Setpoint 4

[-06] =

Setpoint 5

Setpoint data from main
setpoint (P510 [-01]).

[-07] =

Bus I/O In Bits (P480)

The displayed value depicts
all Bus In Bit sources linked
with or.

[-08]

= Parameter data In 1

[-09]

= Parameter data In 2

[-10]

= Parameter data In 3

[-11]

= Parameter data In 4

[-12]

= Parameter data In 5

Data during parameter
transfer: Order label (AK),
Parameter number (PNU),
Index (IND), Parameter
value (PWE 1/2)

0000 ... FFFF (hex) This parameter informs

about the actual control
word and the setpoints
that are transferred via
the bus systems.

For display, a BUS
system must be selected
in P509

[-13]

= Setpoint 1

[-14]

= Setpoint 2

[-15]

= Setpoint 3

[-16]

= Setpoint 4

[-17]

= Setpoint 5

Setpoint data from the
master function value
(Broadcast), if P509 = 9/10
(P510 [-02])

[-18]

= PLC control word

Control word, source PLC

[-19]

= Setpoint 1

[-20]

= Setpoint 2

[-21]

= Setpoint 3

[-22]

= Setpoint 4

[-23]

= Setpoint 5

Setpoint data from the PLC.

P741

[-01]

...
[-13]

PZD bus out

(Process data bus out)

up to

SK 535E

S

[-01 ] = Status word

Status word, source from
P509.

[-02]

= Actual value 1 (P543)

[-03]

= Actual value 2 (P544)

[-04]

= Actual value 3 (P545)

[-05] =

Bus I/O Out Bit (P481)

The displayed value depicts
all Bus Out Bit sources
linked with or.

[-06 ]

= Parameter data Out 1

[-07 ]

= Parameter data Out 2

[-08]

= Parameter data Out 3

[-09]

= Parameter data Out 4

[-10] =

Parameter data Out 5

Data during parameter
transfer.

0000 ... FFFF (hex) This parameter provides

information about the
actual status word and
the actual values that are
transferred via the bus
systems.

[-11] =

Actual value 1 master function

[-12] =

Actual value 2 master function

[-13] =

Actual value 3 master function

Actual value of master
function 502/P503.