3 Commissioning
3.1 Cabling
3.1.1
Topology
The SK TU3-PNT PROFINET IO modules can be connected to each other in star, tree, linear or ring
topologies.
Fig. 5: Example of PROFINET IO linear topology
Fig. 6: Example of PROFINET IO star topology with switch
3.1.2
EMC
If EMC measures are not in place, high-frequency interference which is mainly caused by switching
processes or lightning often causes electronic components in the bus participants to be faulty and error-free
operation can no longer be ensured.
Correct laying of the bus cable dampens the electrical influences which may occur in an industrial
environment. The following points must be observed:
Implement long connections between bus participants by the shortest possible distances.
Only use plugs with a metal housing.
For the production of bus cables lay the shielding on as wide an area of the plug as possible.
With the parallel installation of bus cables, a minimum distance of 20 cm from should be maintained from
other cables carrying a voltage greater than 60V. In particular, this must be observed for cables to
motors or chopper resistors. This applies to lines laid both inside and outside of control cabinets.
The minimum distances for parallel installation may be reduced by shielding cables carrying voltage or
by means of earthed metal dividers in the cable ducts.
Connect SK TU3- Ethernet module to the PE (Connection via the plug pin next to the 24V supply).
PROFINET
IO Controller
TU3-PNT
TU3-PNT
TU3-PNT
PROFINET
IO Controller
Switch
TU3-PNT
TU3-PNT
TU3-PNT