4 Communication

BU 0590 GB-0312

Subject to technical amendments

25

4.2 Parameter transfer

4.2.1

Function of PROFINET Records

The transfer of parameter data (Records) is performed acyclically. All parameters of the FI and the bus
module can be accessed. For this the parameters of the SK TU3-PNT are assigned to Slot 2 and the
parameters of the frequency inverter to Slot 3.
The illustration below describes the function of Records



























Fig. 11 Function of PROFINET Record

 By means of a "Write Request" the data record is transferred to the IO device (SK TU3-PNT) as a

parameter order.

 With "Write Response" the IO controller receives confirmation of the receipt of the message.
 The IO controller requests a response from the SK TU3-PNT with "Read Request".
 The SK TU3-PNT responds with a "Read Response (-)", if processing is not yet complete.
 After processing of the parameter in the SK TU3-PNT the parameter order is concluded with the

transfer of the parameter response to the IO controller by means of "Read Response (+)".

IO Controller


Parameter
order

PROFINET Record

IO Device


Parameter
order

Parameter
response

Write Request

Slot 3

Read Request

Slot 3

Read Response (-)

Slot 3

Read Request

Slot 3

Write Response

Slot 3

Read Response (+)

Slot 3

Parameter
response