Examples – NORD Drivesystems BU0590 User Manual
Page 30
PROFINET bus module for NORD frequency inverters SK 5xxE
30
Subject to technical amendments
BU 0590 GB-0312
4.2.4
Examples
4.2.4.1
Reading of module parameter P170 Index 0 (actual error)
Data record 100 is used:
Field
Data size
Byte
Date
Explanation
Order label
+
Parameter number
2 Byte
2
01 h
+492 h
_________
1492 h
Read parameter value (see Section 4.2.3 )
+
Parameter number P170 (+1000) = 492 h
Parameter index
2 Bytes
3
4
00 h
00 h
Parameter sub-index (see Section 4.2.3.2)
Parameter value
4 Bytes
5
6
7
8
00 h
00 h
00 h
00 h
Setting value not set with read order
Table 26 Example telegram for reading parameter P170
S7 Code example:
CALL "WRREC" , DB53
WriteRequest
REQ :=#bStart
ID :=DW#16#7FC
Diagnosis address
INDEX
:=100
Data set 100
LEN :=8
Length: 8 Bytes
DONE :=#bEnde
BUSY :=#bBusy
ERROR :=#bError
STATUS:=#wStatus
RECORD:=P#DB10.DBX0.0 BYTE 8
Data: 14h,92h, 00h,00h, 00h,00h, 00h,00h
CALL "RDREC" , DB52
ReadResponse
REQ :=#bStart
ID :=DW#16#7FC
Diagnosis address
INDEX
:=100
Data set 100
MLEN :=8
VALID := …
BUSY := …
ERROR := …
STATUS:= …
LEN := …
RECORD:=P#DB10.DBX12.0 BYTE 8
Response: 14h,92h, 00h,00h, 00h,00h, 03h,FCh
The value read is P170 = 1020 (03FCh).