4.2.2
Data records
4.2.2.1
Data records 100 and 101
The data records are written to Slot 0. The number of the data record determines the relevant target device.
For this:
DS 100 Access to the technology unit (parameter range 150…199)
DS 101 Access to the frequency inverter (parameter range 0 … 999, except 150…199)
NOTE
The inverter parameters are mapped in the range 1000 to 1999, i.e. 1000 must be added to the
parameter number for parameterisation (e.g. (P508) - P1508).
Field
Data size
Explanation
Parameter number
and
Order label
2 Bytes
FI or SK TU3 parameter
The parameter number is a 16 Bit value (+1000) and can be obtained from
the relevant operating manual for the frequency inverter or technology unit.
The order label is added to the parameter number. (upper Nibble)
Parameter index
2 Bytes
Parameter sub-index (see Section 4.2.3.2)
Parameter value
4 Bytes
New setting value (See Section 4.2.3.3).
Table 19 Structure of data records 100 and 101
4.2.2.2
Data record 47
This data record is written to Slot 0 and is then assigned to the relevant device on the basis of the axis. The
format is compliant withe the ProfiDrive profile.
Field
Data size
Explanation
Order reference
1 Byte
The order reference is transferred from the IO controller and is used for the
definitive allocation of the SK TU3-PNT response
Order label
1 Byte
Read / write parameter value etc. (see Section 4.2.3 )
Axis
1 Byte
Access to SK TU3-PNT parameter or FI parameter
0 = SK TU3-PNT
1 = Frequency inverter
Parameter number
2 Bytes
FI or SK TU3 parameter
The parameter number is a 16 Bit value (+1000) and can be obtained from
the relevant operating manual for the frequency inverter or technology unit.
Parameter index
2 Bytes
Parameter sub-index (see Section 4.2.3.2)
Parameter value
4 Bytes
New setting value (See Section 4.2.3.3).
Table 20 Structure of data record 47
4.2.2.3
Transfer of data record via PPO 1 and PPO 2
PPO1 and PPO2 objects are supported in order to simplify the conversion of an existing PROFIBUS system
to a PROFINET system. In addition to the cyclical IO data, there are also the acyclical parameter data (see
Section 4.2.4.4).