NORD Drivesystems BU0590 User Manual
Page 35
Fehler! Verweisquelle konnte nicht gefunden werden.Fehler! Verweisquelle konnte nicht gefunden werden.
BU 0590 GB-0312
Subject to technical amendments
35
Parameter
{Factory setting}
Setting value / Description / Note
Device
Parameter
type
P162
Device name
(Device name)
SK TU3-PNT
8 Bit
45 ... 122
The device name can be queried or changed with this parameter. Character strings with a
length of up to 240 characters are possible. Characters 45 to 122 from the ASCII Code can be
used.
The name is saved after the entry of a 0 at the end of the character string.
P163
…
[-01]
…
…
[-07]
Test alarm
(Test alarm)
SK TU3-PNT
8 Bit
This parameter is used, e.g to trigger a diagnostic alarm from a slot during commissioning. A
frequency inverter error can be simulated by entering the value of the error (e.g. link circuit
overvoltage = E005.0 Value 50) in the slot of the relevant inverter (e.g.: Slot 3). An
"incoming" alarm is triggered. If the value is reset to 0 the alarm is "outgoing".
Example:
Trigger alarm with error 5.0 on Slot 2:
P163[-04] = 50 ChannelErrorType=
0x100+50=0x132
0 ... 255
all { 0 }
[-01] =
Slot 0 (DAP - reserved)
[-02] =
Slot 1 (reserved)
[-03] =
Slot 2 (TU)
[-04] =
Slot 3 (FI)
[-05] =
Slot 4 (reserved)
[-06] =
Slot 5 (reserved)
[-07] =
Slot 6 (reserved)
5.1.3
BUS module information parameters, general (P17x)
Access:
Read
only
Parameter
Setting value / Description / Note
Device
Parameter
type
P170
...
…
[-02]
Present error
(Present error)
SK TU3-PNT
16 bit
Actual errors in the PROFINET module. The error message is reset when the supply voltage is
switched off.
Possible error codes:
- 1020 Bus Time Out via P151 (TU4-PNT) or P513 (TU3-PNT)
0 ... 5420
[-01] =
Actual module error
[-02] =
Actual module error
P171
…
[-01]
…
…
[-03]
Software-Version
(Software Version / Revision)
SK TU3-PNT
16 bit
This parameter shows the software and revision numbers in the module. Array 03 provides
information about any special versions of the hardware or software A zero stands for the
standard version.
0.0 ... 9999.9
[-01] =
Version
[-02] =
Revision
[-03] =