PROFINET bus module for NORD frequency inverters SK 5xxE
36
Subject to technical amendments
BU 0590 GB-0312
Parameter
Setting value / Description / Note
Device
Parameter
type
P172
Configuration
(Configuration level)
SK TU3-PNT
16 bit
The version can be queried in this parameter.
0 ... 2
Possible values:
0 = Internal module
, (SK CU4)
1 = External module
, (SK TU4)
2 = Module SK TU3-PNT
P173
Option status
(Module status)
SK TU3-PNT
16 bit
0 ... 0xFFFF
Explanation of bits:
Bit 0 = Initialisation
Bit 1 = AR installed
Bit 2 = Reserved
Bit 3 = Timeout (P151 / P513)
Bit 4 = Reserved
Bit 5 = Ethernet connection
Bit 6 = Reserved
Bit 7 = Reserved
Bit 8 = Frequency inverter status
Bit 9 = Frequency inverter status
Explanation of frequency inverter status
Bit9 | Bit8
0
0
FI is offline
0
1
FI not supported
1
0
FI is online
P176 …
[-01]
…
…
[-27]
PZD bus IN
(Process data bus IN)
SK TU3-PNT
16 bit
Allocation of process data which have been received (data sent from PROFINET IO controller).
-32768 ... 32767
[-01] =
Bus module outputs
[-02] =
Control word for FI1
[-03] =
Setpoint 1 for FI1
[-04] =
Setpoint 2 for FI1
[-05] =
Bus module outputs
[-06] =
Control word for FI1
[-07] =
Setpoint 1 for FI1
[-08] =
Setpoint 2 for FI1
P177
…
[-01]
…
…
[-27]
PZD bus OUT
(Process data bus OUT)
SK TU3-PNT
16 bit
Allocation of process data which have been transmitted (data sent to the PROFINET IO
controller).
-32768 ... 32767
[-01] =
Bus module inputs
[-02] =
Status word from FI1
[-03] =
Actual value 1 from FI1
[-04] =
Actual value 2 from FI1
[-05] =
Bus module inputs
[-06] =
Status word from FI1
[-07] =
Actual value 1 from FI1
[-08] =
Actual value 2 from FI1