background image

PROFINET bus module for NORD frequency inverters SK 5xxE

36

Subject to technical amendments

BU 0590 GB-0312

Parameter

Setting value / Description / Note

Device

Parameter
type

P172

Configuration

(Configuration level)

SK TU3-PNT

16 bit

The version can be queried in this parameter.

0 ... 2

Possible values:

0 = Internal module

, (SK CU4)

1 = External module

, (SK TU4)

2 = Module SK TU3-PNT

P173

Option status

(Module status)

SK TU3-PNT

16 bit

0 ... 0xFFFF

Explanation of bits:

Bit 0 = Initialisation
Bit 1 = AR installed
Bit 2 = Reserved
Bit 3 = Timeout (P151 / P513)
Bit 4 = Reserved
Bit 5 = Ethernet connection
Bit 6 = Reserved
Bit 7 = Reserved
Bit 8 = Frequency inverter status
Bit 9 = Frequency inverter status

Explanation of frequency inverter status

Bit9 | Bit8
0

0

FI is offline

0

1

FI not supported

1

0

FI is online

P176 …

[-01]


[-27]

PZD bus IN

(Process data bus IN)

SK TU3-PNT

16 bit

Allocation of process data which have been received (data sent from PROFINET IO controller).

-32768 ... 32767

[-01] =

Bus module outputs

[-02] =

Control word for FI1

[-03] =

Setpoint 1 for FI1

[-04] =

Setpoint 2 for FI1

[-05] =

Bus module outputs

[-06] =

Control word for FI1

[-07] =

Setpoint 1 for FI1

[-08] =

Setpoint 2 for FI1

P177

[-01]


[-27]

PZD bus OUT

(Process data bus OUT)

SK TU3-PNT

16 bit

Allocation of process data which have been transmitted (data sent to the PROFINET IO
controller).

-32768 ... 32767

[-01] =

Bus module inputs

[-02] =

Status word from FI1

[-03] =

Actual value 1 from FI1

[-04] =

Actual value 2 from FI1

[-05] =

Bus module inputs

[-06] =

Status word from FI1

[-07] =

Actual value 1 from FI1

[-08] =

Actual value 2 from FI1