2 error messages in the ethercat module sk tu3-ect, 3 error messages in the sk 5xxe frequency inverter – NORD Drivesystems BU0570 User Manual
Page 38
EtherCAT bus module for NORD frequency inverters SK 5xxE
38
Subject to technical amendments
BU 0570 GB-0312
Error code
Error register
FI Error Code
Explanation
0x8111
17
10.3 / 10.4 /
10.5 / 10.6 /
10.7 / 10.9
0x8300
1 13.2
0x8400
1 13.1
0x9000
1 12.0
0xFF00
129 18.0
0xFF10
129 19.0
Table 21 Assignment of Emergency Error Codes to the FI Error Codes
6.2 Error messages in the EtherCAT module SK TU3-ECT
All SK TU3-ECT error messages are displayed in parameter (P170) of the bus module and trigger an error
in the connected FI. This is permanently stored in the FI error statistics. The error messages in the bus
module memory (P170) parameter are lost when the 24V supply voltage is switched off.
6.3 Error messages in the SK 5xxE frequency inverter
Errors cause the frequency inverters to switch off, in order to prevent a device fault.
The following options are available to reset a fault (acknowledge):
1. Switching the mains off and on again,
2. By an appropriately programmed digital input (P420 ... P425 / P470 = Function 12),
3. By switching of the “enable” on the frequency inverter (if no digital input is programmed for
acknowledgement),
4. By Bus acknowledgement or
5. By P506, the automatic error acknowledgement.
The following error messages are directly associated with the Bus module SK TU3-ECT.
FI Error Code
Error register
0 No
error
10.1
No communication with the EtherCAT- ASIC.
The ASIC error can only be reset by switching
off the 24V supply voltage of the TU3-ECT
10.2 Timeout
EtherCAT
Watchdog
10.3
Timeout via P513 monitoring
10.5 General
EtherCAT
configuration error
10.8
The connection between the FI and the SK TU3-ECT had a timeout
Table 22 SK5xxE error messages associated with the SK TU3-ECT
For a complete overview of the error messages relating to the frequency inverter, please refer to the
frequency inverter manual BU0500.