NORD Drivesystems BU0570 User Manual
Page 24
EtherCAT bus module for NORD frequency inverters SK 5xxE
24
Subject to technical amendments
BU 0570 GB-0312
4.2.6
Beispiel für FU das Ein- / Ausschalten des Frequenzumrichters
In this example, a FI will be operated with a setpoint (setpoint frequency) and an actual value (actual
frequency). The "Maximum Frequency" is 50Hz.
Parameter settings:
P105 = 500
P543 = 1
P546 = 1
Control
word
Setpoint 1
Status word
Actual
value 1
Explanation
- - -
- - -
0000h
0000h
- - -
- - -
xx40h
0000h
The mains voltage is switched on at the FI
047Eh
0000h
xx31h
0000h
FI is set to "Standby" status
047Fh
2000h xx37h 2000h
FI is set to "Operation enabled" status and controlled with a
50% setpoint.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 25Hz.
0047Eh
2000h xx31h 0000h
FI is set to "Standby" status, the motor runs up its
parameterised ramp to speed 0 and is switched off.
The FI is disabled again and the motor is without current.
047Fh
1000h xx37h 1000h
FI is set to "Operation enabled" status and controlled with a
25% setpoint.
The FI is enabled, the motor is supplied with current and rotates with a frequency of 12.5Hz.
Table 17 Example of setpoint specification
4.2.7
Timeout monitoring
Data traffic on the EtherCAT side is monitored by EtherCAT watchdogs. Monitoring via the FI parameter
P513 is also possible.
P513 monitoring is triggered if the process data contact is interrupted or the process data is transferred with
an invalid control word (Bit10 in control word = 0). This function is activated when the first valid process data
telegram is received.