beautypg.com

NORD Drivesystems BU0570 User Manual

Page 34

background image

EtherCAT bus module for NORD frequency inverters SK 5xxE

34

Subject to technical amendments

BU 0570 GB-0312

5.2.2

Information parameters

Access:

Read

only

Parameter

Setting value / Description / Note

Device

Parameter
type

P740

[-01]

...
[-13]

PZD bus in

(Process data bus in)

up to

SK 535E

S

[-01]

= Control word

Control word, source from
P509.

[-02]

= Actual bus value 1

[-03]

= Actual bus value 2

[-04] =

Setpoint 3

Setpoint data from main
setpoint (P510 [-01]).

[-05] =

Bus I/O In Bits (P480)

The displayed value depicts all
Bus In Bit sources linked with
or

.

[-06]

= Parameter data In 1

[-07]

= Parameter data In 2

[-08]

= Parameter data In 3

[-09]

= Parameter data In 4

[-10]

= Parameter data In 5

Data during parameter transfer:
Order label (AK),
Parameter number (PNU),
Index (IND), Parameter value
(PWE 1/2)

0000 ... FFFF (hex) This parameter informs

about the actual control
word and the setpoints that
are transferred via the bus
systems.

For display, a BUS system
must be selected in P509

[-11]

= Setpoint 1

[-12]

= Setpoint 2

[-13]

= Setpoint 3

Setpoint data from the master
function value (Broadcast), if
P509 = 9/10
(P510 [-02])

P740

[-01]

...
[-23]

PZD bus in

(Process data bus in)

SK 540E

and above

S

[-01]

= Control word

Control word, source from
P509.

[-02]

= Actual bus value 1

[-03]

= Actual bus value 2

[-04] =

Setpoint 3

[-05] =

Setpoint 4

[-06] =

Setpoint 5

Setpoint data from main
setpoint (P510 [-01]).

[-07] =

Bus I/O In Bits (P480)

The displayed value depicts all
Bus In Bit sources linked with
or

.

[-08]

= Parameter data In 1

[-09]

= Parameter data In 2

[-10]

= Parameter data In 3

[-11]

= Parameter data In 4

[-12]

= Parameter data In 5

Data during parameter transfer:
Order label (AK),
Parameter number (PNU),
Index (IND), Parameter value
(PWE 1/2)

0000 ... FFFF (hex) This parameter informs

about the actual control
word and the setpoints that
are transferred via the bus
systems.

For display, a BUS system
must be selected in P509

[-13]

= Setpoint 1

[-14]

= Setpoint 2

[-15]

= Setpoint 3

[-16]

= Setpoint 4

[-17]

= Setpoint 5

Setpoint data from the master
function value (Broadcast), if
P509 = 9/10
(P510 [-02])

[-18]

= PLC control word

Control word, source PLC

[-19]

= Setpoint 1

[-20]

= Setpoint 2

[-21]

= Setpoint 3

[-22]

= Setpoint 4

[-23]

= Setpoint 5

Setpoint data from the PLC.