NORD Drivesystems BU0570 User Manual
Page 36
EtherCAT bus module for NORD frequency inverters SK 5xxE
36
Subject to technical amendments
BU 0570 GB-0312
Parameter
Setting value / Description / Note
Device
Parameter
type
P745
Option version
(Module version)
SK 5xxE
0.0 ... 999.9
Version status (software version) of the technology unit (SK TU3-xxx), but only when own
processor is present, therefore not for SK TU3-CTR.
Have this data available if you have a technical query.
P746
Option status
(Module status)
SK 5xxE
S
0000 ... FFFF (hex)
Actual status (readiness, error, communication) of the technology unit (SK TU3-xxx), but only
when own processor is present, therefore not for SK TU3-CTR.
Possible values:
Bit 0
= EtherCAT state "Pre- Operational"
Bit 1
= EtherCAT state "Save- Operational" or "Operational"
Bit 2
=
Vacant
Bit 3
=
Vacant
Bit 4
= Error 1
Bit 5
= Error 2
Bit 6
= Error 3
Bit 7
=
Vacant
Bit 8 – Bit 15 = Module number (EtherCAT = 20)
Error table
Error 3 | Error 2 | Error 1 |
Meaning
0 0 0
No error
0 0 1
EtherCAT ASIC cannot be accessed
0 1 0
EtherCAT watchdog timeout
0 1 1
P513 timeout
1 0 0
General EtherCAT configuration error
NOTE
When activated, the functions block current, quick stop, remote control and cancel error
are available at the (local) control terminals. To operate the drive, a high signal must be
present on the digital inputs being used before the drive can be enabled.