NORD Drivesystems BU0570 User Manual
Page 21
4 Communication
BU 0570 GB-0312
Subject to technical amendments
21
4.2.4
FI Status Machine
The frequency inverter passes through a status machine. The changes between various states are triggered
by the respective control commands in the process data control word. The actual status is returned in the
process data status word.
After switching on, the inverter is in switch-on disabled status. This status can only be ended by
transmitting the “Shut down (Off 1)” command.
The answer to a master telegram normally does not yet contain a reaction to the control command. The
controller has to check the answers from the slaves as to whether the control command has been carried
out.
Status
Bit 6
Switch-on
disable
Bit 5
Emergency
stop
Bit 4
Disable
voltage
Bit 3
Fault
Bit 2
Operation
enabled
Bit 1
Standby
Bit 0
Ready for
switch-on
Not ready to start
0
X
X
0
0
0
0
Starting
disabled 1 X X 0 0 0 0
Ready
to
start
0 1 1 0 0 0 1
Activated
0 1 1 0 0 1 1
Operation
enabled
0 1 1 0 1 1 1
Fault
0 X X 1 0 0 0
Error
active
0 X X 1 1 1 1
Emergency stop
active
0 0 1 0 1 1 1
Table 15 Codes for FI status