6 Error monitoring and error messages

BU 0570 GB-0312

Subject to technical amendments

37

6 Error monitoring and error messages

According to the cause, frequency inverters and technology units generate appropriate messages if they
deviate from their normal operating status.

6.1 EtherCAT error monitoring

In case of FI errors, SK TU3-ECT sends an error message on the EtherCAT bus via Emergency Message
(CoE). The message is structured as follows.

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Error code

Error

Register

FI-ID

Not used

Table 20 Structure of Emergency Message ( CoE )


FU ID = identifies the FI from which the error message has come  FI1 = 1, FI2 = 2, etc. (for TU3-ECT = 1)

Error code

Error register

FI Error Code

Explanation

0x0000 0

0

No

error

0x1000

1

? ? ?

General error  the FI error code cannot be assigned

0x2200

3

4.0 / 4.1

0x2310

3 3.0

0x2311

3 3.2

0x2312

3 3.3

0x3110

5 5.1

0x3120

5 6.1

0x3130

5 7.0

0x3210

5 5.0

0x3230

5 6.0

0x4210

9 1.1

0x4310

9

2.0 / 2.1 / 2.2

0x5000

1 10.8

0x5110

1 11.0

0x5300

1 17.0

0x5510

1 20.0

0x5520

1 20.8

0x5530

1 8.2

0x6000

1

20.1 to 20.7 /

21.3

0x7112

3 3.1

0x7120

1

16.0 / 16.1

0x7305

1 13.0

0x8100

17

10.0 / 10.1 /

10.2