2 commissioning the bus module 3.2.1 – NORD Drivesystems BU0570 User Manual
Page 14
EtherCAT bus module for NORD frequency inverters SK 5xxE
14
Subject to technical amendments
BU 0570 GB-0312
3.2 Commissioning the bus module
3.2.1
Connecting the bus module
Connect the bus module to the PE via the plug pins
Connect the 24V supply via the plug-in terminal. Note the consumption of each module
(Technical Data)
Connect the Ethernet cable
Bus direction
EtherCAT
Incoming cable
(from master /
controller)
Left RJ45 socket
Labelled "IN"
Outgoing cable
Right RJ45 socket
Labelled "OUT"
Table 8 Bus cable connections
If the bus module is the last participant, the RJ45 socket remains open in the outgoing direction. The
bus connection is performed automatically.
ATTENTION
Each bus module requires a separate PE connection via the plug pin. Otherwise,
interference-free operation of the bus module cannot be guaranteed.
3.2.2
Parameter settings of the frequency inverter
The following settings must be made on the frequency inverter (SK5xxE):
Control via
Ethernet TU P509 = "8"
Setpoint via
Ethernet TU P510 = "8" or "0" if P509 = "8"
Setting of setpoints via
P546, P547 and P548 (SK 500E … SK 535E)
P546 [-01] … [-05] (SK 540E and above)
Setting of actual values via
P543, P544 and P545 (SK 500E … SK 535E)
P543 [-01] … [-05] (SK 540E and above)
For a detailed description of the parameters, please refer to the frequency inverter operating manual
(BU 0500).
The parameters can be set with NORD parameterisation tools (e.g. NORD CON, SimpleBox) or via the bus
master / controller.