4.3 Parameterübertragung EtherCAT
4.3.1
Ablauf der Parameterübertragung
The transfer of parameter data is carried out cyclically with low priority. Transfer is carried out in CoE (CAN
over Ether CAT) protocol via the SDO transfer. All parameters of the FI and the bus module can be
accessed.
The parameter numbers stated in the documentation must be converted into the numerical range specified
for EtherCAT. This is performed according to the following formula:
SK TU3-ECT parameter = NORD parameter number + 2000h
SK 5xxE parameter
= NORD parameter number + 2800h
Example:
The FI parameter P102 is accessed via EtherCAT with the parameter number 2866h (10342dec).
For parameters with a sub-index, the first value is always on sub-index 1. Sub-index 0 contains the
maximum size of the array.
The processing of SDP parameter access is complex and will not be described here. In general, the
EtherCAT SPS provides functional modules for this purpose.
4.3.2
Error codes for SDO parameter access
In case of failure of parameter access, one of the error codes listed in the table below is sent.
Error code in hex
Explanation
0x05 03 00 00
Toggle bit has not changed status
0x05 04 00 00
Timeout of the SDO response by the bus module
0x05 04 00 01
Unknown SDO command
0x05 04 00 05
Insufficient memory
0x06 01 00 00
Access not supported
0x06 01 00 01
Reading access to write-only parameter
0x06 01 00 02
Writing access to a read-only parameter
0x06 02 00 00
Access to a non-existent parameter
0x06 04 00 43
Incompatible parameter
0x06 04 00 47
Internal incompatibility in module
0x06 06 00 00
Hardware error
0x06 07 00 10
Invalid parameter type
0x06 07 00 12
Parameter access with excess data length
0x06 07 00 13
Parameter access with insufficient data length
0x06 09 00 11
Parameter sub-index does not exist
0x06 09 00 30
Parameter value range overflow
0x06 09 00 31
Parameter value too large
0x06 09 00 32
Parameter value too small
0x06 09 00 36
Maximum value smaller than the minimum value
0x08 00 00 00
General error
0x08 00 00 20
Parameters cannot be read or stored in the FI, as there is no connection
between the SK TU3-ECT and the FI
Table 18 Error codes for parameter access failure