NORD Drivesystems BU0570 User Manual
Page 11
2 Modules
BU 0570 GB-0312
Subject to technical amendments
11
2.2.4
Status display via LED
RUN
ERR
DS DE
L / A*
*L / A = Link / Aktiv: auf jeder RJ45 Buchse vorhanden
Fig. 4 Location and designation of the LEDs
RUN
Green LED
State
Meaning
Off
Init
No communication of process data and parameters
Flashing
Pre-Operational
- Parameter communication active
- No process data communication
Single Flash
Save Operational
- Parameter communication active
- Limited process data communication
- No restrictions to actual values
- Setpoints not evaluated
On
Operational
- Parameter communication active
- Unrestricted process data communication
Table 4 Description of the RUN LED (Ethernet Status)
ERR
Red LED
State
Meaning
Off
No Error
EtherCAT functioning normally on the Bus Module
Flashing
Invalid Configuration
General EtherCAT configuration error, can be generated by a false
XML file.
Single Flash
Unsolicited State
Change
SK TU3-ECT has changed the EtherCAT state without authorisation
Double Flash
Application Watchdog
Timeout
EtherCAT or FI timeout (P513 in FI)
Table 5 Description of the ERR LED (Ethernet Status)
L/A
Green LED
State
Meaning
Off
No Connection
No connection via cable or the SK TU3-ECT has no power supply
Flashing
Active
Connected and active
ON
Inactive
Connected, but no bus activity
Table 6 Description of the Link / Activity LEDs