2 process data, Process data structure – NORD Drivesystems BU0570 User Manual
Page 18
EtherCAT bus module for NORD frequency inverters SK 5xxE
18
Subject to technical amendments
BU 0570 GB-0312
4.2 Process data
Control words and setpoints are transferred from the bus master to the SK TU3-…bus module as process
data and in return, the status word and actual values are sent to the bus master / controller from the FI.
Transfer is carried out cyclically. The bus master / controller can access these process values directly, as
they are stored in the I/O area.
For EtherCAT the length and structure of the process data are fixed and are determined by the XML-File.
According to the SK TU3-ECT / FI combination, 4 or 6 process values are available.
The allocation of the values transferred in the setpoint/actual value area of the FI is made via the
parameters P543 to P548 or P543 [-01]…[-05].
4.2.1
Process data structure
The structure of the process data is defined by the XML file.
Direction of
transmission
Transmitted data
( 8 Byte )
1st
word
2nd word
3rd word
4th word
... to SK TU3
Control word
Setpoint 1
Setpoint 2
Setpoint 3
... from the SK TU3
Status word
Actual
value 1
Actual
value 2
Actual
value 3
Table 11: Process data structure SK 500E to SK 535E
Direction of
transmission
Transmitted data
( 12 Byte )
1st word
2nd word
3rd word
4th word
5th word
6th word
... to SK TU3
Control word
Setpoint 1
Setpoint 2
Setpoint 3
Setpoint 4
Setpoint 5
... from the SK TU3
Status word
Actual
value 1
Actual
value 2
Actual
value 3
Actual
value 4
Actual value 5
Table 12: Process data structure SK 540E to SK 545E