beautypg.com

Dwyer 2600 User Manual

Page 47

background image

May, 2013

Page 47 of 52

949-1194 Rev. 7

Control Output Ratings:

SSR: 2.5 A @ 240 Vac at 25°C (77°F). Derates to 1.25 A @ 55°C (130°F);
Relay: SPDT, 10 A @ 240 VAC resistive; 1/2 hp @ 120 VACor 1/3 hp @ 240 VAC;

Alarm Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive. Pilot Duty

Rating: 240 VA, 2A @ 120 VAC or 1A @ 240 VAC.
Current (isolated): 0 to 20 mA across 600 ohms maximum.
Switched Voltage (isolated): 15 VDC @ 20 mA.

Panel Cutout: 92 mm x 92 mm (3.625˝ x 3.625˝).
Depth Behind Mounting Surface: 103 mm (4.0˝) maximum.
Weight: 454 g (16 oz).
Agency Approvals: UL, C-UL E83725; CE.
Front Panel Rating: IP66, (UL Type 4X).

OPTIONS
-924 Analog Remote Set Point

Input: 0 to 10 VDC
Input Impedance: 1 Meg Ohms
Isolation: Shares common ground with PV input.
Scale: Programmable from 100 to 11998 counts, depending on PV range selected.

-926 Analog Remote Set Point

Input: 0 to 20 mADC.
Input Impedance: 10 Ohms
Isolation: Shares common ground with PV input.
Scale: Programmable from 100 to 11998 counts, depending on PV range selected.

-928 Analog Remote Set Point

Input: 0 to 10,000 ohms, two wire.
Search Current: 4 μA.
Isolation: Shares common ground with PV input.

-934 Analog Retransmission of PV/SV (programmable)

Output: 0 to 20 mADC into 600 Ohms, maximum.
Isolation: 500 VAC
Scale: Programmable from 100 to 11998 counts, depending on PV range selected.

-936 Analog Retransmission of PV/SV (programmable)

Output: 0 to 10 VDC @ 20 mA maximum.
Isolation: 500 VAC
Scale: Programmable from 100 to 11998 counts, depending on PV range selected.

-948 Four Stage Set Point

Input: Dry contact or Transistor switch (NPN open collector type).
Current: 1 mADC.
Isolation: Shares common ground with PV input.