Dwyer 2600 User Manual
Page 40

May, 2013
Page 40 of 52
949-1194 Rev. 7
S P S A
(Option 948, 4-Stage Set Point) Switch Action: Select r E or I n t .
r E
Set Point Stage selected by external contact closures.
I n t
Set Point Stage selected by internal menu selection. See S P menu item
in Secondary Menu.
A d d r
(Option 992, 993, 995, 996, Serial Communications) Control Address: Set from 1
to 3 F F for Options 992 and 993. Set from 1 to F F for Options 995 and 995. This
number (hexadecimal, base 16) must match the address number used by the
host computer. Power to instrument must be turned off and on before change
takes effect (see Page 21).
b A U d
(Option 992, 993, 995, 996, Serial Communications) Communication Baud Rate:
Select 3 0 0 , 1 2 0 0 , 2 4 0 0 , 4 8 0 0 , 9 6 0 0 (baud), 1 9 . 2 , or 2 8 . 8 (kbaud) This number
must match the baud rate used by the host computer. Power to instrument must
be turned off and on before change takes effect (see Page 21).
n A t
(Option 992, 993, 995, 996, Serial Communications) No Activity Timer: Select
O F F or 1 to 9 9 minutes.
1 - 9 9
Maximum time between host computer accesses. If the timer counts to
0, C H E C L o r E will be displayed.
O F F
No Activity Timer function is disabled.
S t o r
(Option 992, 993, 995, 996, Serial Communications) Store to EEPROM: Select
Y E S or n o . (See additional information on pages 22-23).
Y E S
Menu Item changes made through the Serial Communications are
stored directly to the EEPROM.
n o
Menu Item changes made through the Serial Communications are
stored in RAM.
r S C L
(Option 924, 926, 928, Analog Remote Set Point) Remote Scale Low: Select 100
to 11998 counts below r S C H . The total span between r S C L and r S C H must be
within 11998 counts. Maximum setting range is -1999 to +9999 counts.
r S C H
(Option 924, 926, 928, Analog Remote Set Point) Remote Scale High: Select 100
to 11998 counts above r S C L . The total span between r S C L and r S C H must be
within 11998 counts. Maximum setting range is -1999 to +9999 counts.