beautypg.com

Dwyer 2600 User Manual

Page 36

background image

May, 2013

Page 36 of 52

949-1194 Rev. 7

S 2 r E

Set Point 2 Reset. Select O n O F or H o l d .
O n O F

Output will automatically reset when process passes back through
S P 2 d .

H o l d

Manual Reset. Reset (acknowledge) by simultaneously pressing the

INDEX & DOWN ARROW keys for 3 seconds.

S 2 P i

Set Point 2 Power Interrupt. Select O n or O F F .
O n

Alarm Power Interrupt is O n . Output will automatically reset on power-
up if no alarm condition exists.

O F F

Alarm Power Interrupt is O F F . Output will be in the alarm condition on
power-up regardless of condition of process.

S 2 i H

Set Point 2 Inhibit: Select O n or O F F .
O n

Alarm Inhibit is O n . Alarm action is suspended until the process value
first enters a non-alarm condition.

O F F

Alarm Inhibit is O F F .

S 2 L P

Set Point 2 Lamp: Select O o n or O o F F .
O o n

Lamp ON when Output is ON.

O o F F

Lamp OFF when Output is ON.

ALARM TYPE AND ACTION (if alarm function is present)

Caution: In any critical application where failure could cause expensive
product loss or endanger personal safety, a redundant limit controller is
required.

When setting an alarm value for an absolute alarm (A 1 t = A b S ), simply set the value at
which the alarm is to occur.

When setting the alarm value for a deviation alarm (A 1 t = d E ), set the difference in value
from the Set Point desired. For example if a low alarm is required to be 5 degrees below
the Set Point, then set A 1 L o to -5 . If a high alarm is required 20 degrees above the Set
Point, then set A 1 H i to +2 0 . If the Set Point is changed, the alarm will continue to hold the
same relationship as originally set.