Dwyer DPMP-4 User Manual

Dwyer instruments, inc, Series dpmp-4 lcd digital panel meters, Bulletin e-90-dpmp

background image

Series DPMP-4 LCD Digital Panel Meters

Specifications - Installation and Operating Instructions

Bulletin E-90-DPMP

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. Fax: 219/872-9057

e-mail: [email protected]

SPECIFICATIONS
Inputs:
4 to 20 mA.
Input Impedance: 300Ω nominal.
Accuracy: ±(0.1% FS + 2 count).
Power Supply: Powered by control loop.
Backlight Power Supply: 24 VDC @ 35 mA typical.
Span and Zero: Adjustable. (±1999 counts).
Display: 3-1/2 digits, 7 segments, 0.45˝ (11.4 mm) H.
Decimal Points: 3-position, user selectable.
Engineering Units: DPMP-XXX: °F, °C, %, PSI; DPMP-XXXP: V, A,
KW, PF.
Polarity: Automatic, “-” displayed.
Operating Temperature: 32 to 122°F (0 to 50°C).
Storage Temperature: -4 to 158°F (-20 to 70°C).
Mounting: Snap in bezel mount
Connection: Screw terminals.
Conversion Rate: 3 per second.
Warm-Up: 10 minutes typical.
Weight: 2 oz (56.7 g).
Agency Approvals: RoHS.

INSTALLATION
The Series DPMP is designed for panel mounting in a 2.4˝ (61 mm) W x
1˝ (25.4 mm) H panel cutout.

WIRING
The unit is powered by a 4-20 mA loop and the screw terminals for wiring
are located on the back of the adder board marked with + SIG -. The
backlighting requires a 24 VDC power supply and should be connected
to terminals identified with + B/L -.

Note: If backlight supply is not loop supply, ground should be referenced
together.

The Series DPMP LCD Digital Panel Meter provides easy viewing on
the 3-1/2 digit LCD display. The display segments are available in a
choice of amber, red or green. The meter features user-selectable
engineering units, adjustable zero and span and field-selectable decimal
point position. The snap-in bezel mount eliminates mounting hardware
for quick installation. A 24 VDC power supply is required for the
operation of the backlight.

P Models

PANEL CUTOUT FOR

WINDOW MOUNTING

°F

°C

PSI

%

V

A

KW

PF

2-35/64

[64.5]

1-9/64

[29]

2-13/32

[61]

1

[25.4]

1/8

[3]

63/64

[25.1]

1-5/8

[41.1]

2.390 REAR HOUSING

[60.6]

Rear View