If A L 2 is set to O F F and the control is not equipped with options, the Secure Menu ends
here. If A L 2 is set to O F F and the control is equipped with options, proceed to S P S A , A d d r ,
or r S C L below.

If A L 2 is set to E U n t , go to A 2 S t below.

A 2 t

Alarm 2 Type: Select A b S or d E
A b S

Absolute Alarm that may be set anywhere within the values of S C A L
and S C A H and is independent of S P 1 .

d E

Deviation Alarm that may be set as an offset from S P 1 . As S P 1 is
changed the Alarm Point will track with S P 1 . A deviation alarm will also
track any active ramp or soak set point.

A 2 r E

Alarm 2 Reset: Select O n O F or H o l d .
O n O F

Automatic Reset.

H o l d

Manual Reset. Reset (acknowledge) by simultaneously pressing the

INDEX & DOWN ARROW keys for 3 seconds.

A 2 P i

Alarm 2 Power Interrupt: Select O n or O F F .
O n

Alarm Power Interrupt is O n .

O F F

Alarm Power Interrupt is O F F .

A 2 i H

Alarm 2 Inhibit: Select O n or O F F .
O n

Alarm Inhibit is O n . Alarm action is suspended until the process value
first enters a non-alarm condition.

O F F

Alarm Inhibit is O F F .

A 2 S t

Alarm 2 Output State: Select C L O S or O P E n .
C L O S

Closes Contacts at Alarm Set Point.

O P E n

Opens Contacts at Alarm Set Point.

A 2 L P

Alarm 2 Lamp: Select O o n or O o F F .
O o n

Alarm Lamp is ON when alarm contact is closed.

O o F F

Alarm Lamp is OFF when alarm contact is closed.

A 2 L b

Alarm 2 Loop Break. Select O n or O F F .
O n

Loop Break Condition will cause an Alarm Condition.

O F F

Loop Break will not affect the Alarm Condition.