I n P

Input Type: Select one of the following. Refer to the Wiring section for the proper
wiring.

J - I C

Type “J” Thermocouple

C A

Type “K” Thermocouple

E -

Type “E” Thermocouple

t -

Type “T” Thermocouple

L -

Type “L” Thermocouple

n -

Type “N” Thermocouple

r - 1 3

Type “R” Thermocouple

S - 1 0

Type “S” Thermocouple

b -

Type “B” Thermocouple

C -

Type “C” Thermocouple

P 3 9 2

100 ohm Platinum (NIST 0.00392 Ω/Ω/°C)

n 1 2 0

120 ohm Nickel

P 3 8 5

100 ohm Platinum (IEC/DIN 0.00385 Ω/Ω/°C)

1 P 3 8

1000 ohm Platinum (IEC/DIN 0.00385 Ω/Ω/°C)

C u r r

DC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.

U o L t

DC Voltage Input 0.0 to 10.0 or 1.0 to 10.0 volts.

d i F F

DC Voltage Input -10 to +10 mV.

- - - -

Reserved

O S U P

Zero Suppression: Select O n or O F F . Only with Current and Voltage input types.
O F F

The input range will start at 0 (zero) Input.

O n

The input range will start at 4.00 mA or 1.00 V.

U n i t

F , C or n o n E .
F

°F descriptor is On and temperature inputs will be displayed in actual
degrees Fahrenheit.

C

°C descriptor is On and temperature inputs will be displayed in actual
degrees Celsius.

n o n E

°F and °C descriptors will be Off. This is only available with Current and
Voltage Inputs.

d P t

Decimal Point Positioning: Select 0 , 0 . 0 , 0 . 0 0 , 0 . 0 0 0 , o r . 0 0 0 0 . On
temperature type inputs a change here will alter the Process Value, SP1, SP2,
ALLo, ALHi, and InPC. For Current and Voltage Inputs all Menu Items related to
the Input will be affected.
0

No decimal Point is selected. This is available for all Input Types.

0 . 0

One decimal place is available for Type J, K, E, T, L, RTD’s, Current and
Voltage Inputs.

0 . 0 0

Two decimal places is only available for Current and Voltage Inputs.

0 . 0 0 0

Three decimal places is only available for Current and Voltage inputs.

May, 2013

Page 32 of 52

949-1194 Rev. 7