5 source: input signal allocation 21, Configuration – West Control Solutions KS 94 User Manual
Page 19

Span start X0: (only with ratio controller)
Xmin:(min. process value limiting Xmin)
Numeric value: -999 ... 9999
Span end X100: (only with ratio controller)
Xmax:(max. process value limiting Xmax)
Numeric value: -999 ... 9999 and Xmin Xmax
Factor for stoichiometric ratio s: (only with ratio controller)
S:stoichiometric ratio
Numeric value: 00.00 ... 99.99 (2 fixed digits behind decimal point)
Programmer configuration:
(only with programmer configured)
PSel
PwrUp
PEnd
PStrt
(Source for program
selection)
(Behaviour with mains
recovery)
(Behaviour with
program end)
(Source for
Run/Stop)
0: program selection
via operation
1: program selection
via control input
0: continue program
1: stop program and switch over
to Wint
2: continue program after
automatic research
0: continue with following
program
1: following program and
reset (start required)
0: start/stop and
reset together*.
control with
int/ext (without
Option B)
1: start/stop and
reset separate.
(Option B)
3: continue program after successful automatic research
otherwise switch over to Wint
4: continue program at the time mark of mains recovery
*C.190; SWi/e select the source for int/ext-switching.
10.5
SOURCE: Input signal allocation
Input signal allocation is dependent of main controller configuration ‘C.100‘. this proposal must
always be checked before commissioning and corrected, if necessary. Therefore, input signal
allocation ‘SOURCE’ is no independent main item and considered as additional configuration of
‘CONTR’.
Signal allocation analog signals:
S X2
SWext
S dW
S Z
(Signal source for X2
with ratio and
three-element controller)
(Signal source for Wext
with controller with
external set-point)
(Signal source for W
with controller with
set-point offset
(Signal source for
auxiliary variable)
0: X2 switched off
1: X2 of INP5
2: X2 of INP3
0: Wext switched off
1: Wext of INP5
2: Wext of INP6
3: Wext of INP4
0: dW switched off
1: dW of INP5
2: dW of INP6
3: dW of INP4
0: z switched off
1: z of INP3
2: z of INP6
3: z of INP4