3 operating the programmer: 12, 4 calibration: 12, Operation (survey) – West Control Solutions KS 94 User Manual
Page 10: 3 operating the programmer, 4 calibration
Status display:
In the extended operation of KS94, ‘Text2’ indicates the
controller status. The following table shows the possible
displays:
Set-point
Symbol)
Meaning
Status Meaning
Status Meaning
..... Internal set-point
.... No bandalarm and no
programmer active
...
KS94 in local mode
(Front operation
possible)
We
External set-point
Band Band width control has stopped
programmer or set-point ramp.
Rem
KS94 in remote mode
(Front operation
blocked)
Wp
Program set-point
End
End of program is reached
xx.
Segment number
Grw
Set-point gradient is limiting the
speed of change
y
Program number
Rset Programmer in reset mode
W2
2nd set-point
Run
Programmer is running
Stop Programmer has been stopped
9.3
Operating the programmer:
The programmer can be operated (run, stop, reset, preset) with menu 1, via digital inputs or via the
interface (process management system).
Menu 1
(flashes)
Operating Level
When entering the preset time (parameter setting: Pmode = 1) the time can be entered up to 99.59 in
hours . minutes, or only in hours with longer times.
9.4
Calibration:
+
Calibation is only possible with the controller set to manual mode. Calibration from INP1/6 (Typ=
40; Potentiometric transducer) is in two steps.
w
Select x0c Ä Press M (c blinking) Ä set transducer to 0%, wait 6s and confirm with M.
w
Select x100c Ä Press M (c blinking) Ä set transducer to 100%, wait 6s and confirm with M.
Manual calibration of INP6 is only possible with the DAC function switched off. With the DAC
function switched on, automatic calibration is possible (r DAC page 11 ).
w
For selecting YpCal , press Ä M (0 blinks) change to 1 with I and acknowledge with M
r automatic calibration is started.
Operating level
The parameter X0c and X100c can be allocated to the extended operating level.
Operation (survey)
Operating instruction KS94
12
a
>3s
End
Hold
OStar
Para
X0c
End
X100c
X0c
End
X100c
X0c
YpCal
End
Signl
Aux
Input
Contr
Tune
Limit
Setp
I
D
I
D
I
D
I
D
I
D
M
+
+
+
+
+
270
Man.
xw____áûô___ 12%
10.5
M
M
End
INP6
INP1
I
D
M
End
Cal
M
+
M
c
M
+
0
0