Operating Conditions
Ambient Temperature
(Operating):
0
°
C to 55
°
C
Ambient Temperature
(Storage):
–20
°
C to 80
°
C
Relative Humidity:
20% - 95% non-condensing
Supply Voltage:
90 - 264V AC 50/60Hz (standard)
20 - 50V AC 50/60Hz or 22 - 65V DC
(option)
Source Resistance:
1000
Ω
maximum (thermocouple)
Lead Resistance:
50
Ω
per lead maximum balanced (Pt100)
Performance Under Operating Conditions
Temperature Stability:
0.01% of span/
°
C change in ambient
temperature.
Cold Junction
Compensation
(thermocouple Only):
Better than
±
1
°
C.
Supply Voltage Influence:
Negligible.
Relative Humidity
Influence:
Negligible
Sensor Resistance
Influence:
Thermocouple 100
Ω
: <0.1% of span error
Thermocouple 1000
Ω
: <0.5% of span error
RTD Pt100 50
Ω
/lead: <0.5% of span error
A.9
ENVIRONMENTAL
Operating Conditions:
See Subsection A.8 - PERFORMANCE.
Approvals:
CE, UL, ULC
EMI Susceptibility:
Certified to EN50082-1:1992 and
EN50082-2:1995.
NOTE: For line-conducted disturbances
induced by RF fields (10V 80% AM 1kHz),
the
1
16
-DIN controller is self-recoverable in
the frequency bands 17 - 47MHz and 68 -
80MHz.
A-11
S054-A
59125