Max. ON-State Voltage
Drop @ Rated Current:
1.5V peak.
Repetitive Peak OFF-state
Voltage, Vdrm:
600V minimum.
DC
Resolution:
Eight bits in 250mS (10 bits in 1 second
typical, >10 bits in >1 second typical).
Update Rate:
Every control algorithm execution.
Ranges:
0 - 20mA
4 - 20mA
0 - 10V
0 - 5V
(Changes between V and mA ranges also require link jumper movement.)
Load Impedance:
0 - 20mA: 500
Ω
maximum
4 - 20mA: 500
Ω
maximum
0 - 10V: 500
Ω
minimum
0 - 5V: 500
Ω
minimum
Isolation:
Isolated from all other inputs and outputs.
Range Selection Method:
Link jumper or DIP switch and front panel
code.
A.4
OUTPUT 2
General
Types Available:
Relay, SSR drive, solid state and DC.
Relay
Contact Type:
Single pole double throw (SPDT).
Rating:
2A resistive at 120/240V AC.
Lifetime:
>500,000 operations at rated
voltage/current.
Isolation:
Inherent.
A-5
S054-A