Loop control – West Control Solutions N8100 User Manual
Page 73

Max. ON-State Voltage
Drop @ Rated Current:
1.5V peak.
Repetitive Peak OFF-state
Voltage, Vdrm:
600V minimum.
DC
Resolution:
Eight bits in 250mS (10 bits in 1 second
typical, >10 bits in >1 second typical).
Update Rate:
Every control algorithm execution.
Ranges:
0 - 20mA
4 - 20mA
0 - 10V
0 - 5V
(Changes between V and mA require link jumper movement.)
Load Impedance:
0 - 20mA: 500
Ω
maximum
4 - 20mA: 500
Ω
maximum
0 - 10V: 500
Ω
minimum
0 - 5V: 500
Ω
minimum
Isolation:
Isolated from all other inputs and outputs.
Range Selection Method:
Link jumper or DIP.
A.6
LOOP CONTROL
Automatic Tuning Types:
Pre-Tune and Self-Tune.
Proportional Bands:
0 (OFF), 0.5% - 999.9% of input span at
0.1% increments.
Reset (Integral Time
Constant):
1s - 99min 59s and OFF
Rate (Derivative Time
Constant):
0 (OFF) - 99 min 59 s.
Manual Reset (Bias):
Added each control algorithm execution.
Adjustable in the range 0 - 100% of output
power (single output) or –100% to +100%
of output power (dual output).
Deadband/Overlap:
–20% to +20% of Proportional Band 1 +
Proportional Band 2.
S054-A
A-8