Performance under reference conditions – West Control Solutions N8100 User Manual
Page 75
Performance Under Reference Conditions
Common Mode Rejection:
>120dB at 50/60Hz giving negligible effect
at up to 264V 50/60Hz.
Series Mode Rejection:
>500% of span (at 50/60Hz) causes
negligible effect.
DC Linear Inputs
Measurement Accuracy:
±
0.25% of span
±
1LSD.
Thermocouple Inputs
Measurement Accuracy:
±
0.25% of span
±
1LSD. NOTE: Reduced
performance with Type “B” Thermocouple
between 100 - 600
°
C (212 - 1112
°
F).
Linearisation Accuracy:
Better than
±
0.2
°
C any point, any 0.1
°
C
range (
±
0.05
°
C typical). Better than
±
0.5
°
C
any point, any 1
°
C range.
Cold Junction
Compensation:
Better than
±
0.7
°
C.
RTD Inputs
Measurement Accuracy:
±
0.25% of span
±
1LSD
Linearisation Accuracy:
Better than
±
0.2oC any point, any 0.1
°
C
range (
±
0.05
°
C typical). Better than
±
0.5
°
C
any point, any 1
°
C range.
DC Outputs - Accuracy
Output 1:
±
0.5% (mA @ 250
Ω
, V @ 2k
Ω
); 2%
underdrive (4 - 20mA) and overdrive
applies.
Output 2:
±
0.5% (mA @ 250
Ω
, V @ 2k
Ω
); 2%
underdrive (4 - 20mA) and overdrive
applies.
Output 3 (Recorder
Output):
±
0.25% (mA @ 250
Ω
, V @ 2k
Ω
); Degrades
linearly to
±
0.5% for increasing burden (to
specification limits).
S054-A
A-10
59125