Performance Under Reference Conditions

Common Mode Rejection:

>120dB at 50/60Hz giving negligible effect

at up to 264V 50/60Hz.

Series Mode Rejection:

>500% of span (at 50/60Hz) causes

negligible effect.

DC Linear Inputs

Measurement Accuracy:

±

0.25% of span

±

1LSD.

Thermocouple Inputs

Measurement Accuracy:

±

0.25% of span

±

1LSD. NOTE: Reduced

performance with Type “B” Thermocouple
between 100 - 600

°

C (212 - 1112

°

F).

Linearisation Accuracy:

Better than

±

0.2

°

C any point, any 0.1

°

C

range (

±

0.05

°

C typical). Better than

±

0.5

°

C

any point, any 1

°

C range.

Cold Junction

Compensation:

Better than

±

0.7

°

C.

RTD Inputs

Measurement Accuracy:

±

0.25% of span

±

1LSD

Linearisation Accuracy:

Better than

±

0.2oC any point, any 0.1

°

C

range (

±

0.05

°

C typical). Better than

±

0.5

°

C

any point, any 1

°

C range.

DC Outputs - Accuracy

Output 1:

±

0.5% (mA @ 250

, V @ 2k

); 2%

underdrive (4 - 20mA) and overdrive

applies.

Output 2:

±

0.5% (mA @ 250

, V @ 2k

); 2%

underdrive (4 - 20mA) and overdrive

applies.

Output 3 (Recorder

Output):

±

0.25% (mA @ 250

, V @ 2k

); Degrades

linearly to

±

0.5% for increasing burden (to

specification limits).

S054-A

A-10

59125