connecting the resistance element should not exceed 5 ohms per lead (the leads

should be of equal resistance).

1.3.5 Linear Inputs

For linear mA input ranges, connection is made to Terminals 4 and 6 (

1

16

-DIN

controllers) or Terminals 4 and 1 (

1

4

-DIN &

1

8

-DIN controllers) in the polarity shown in

Figures 1-4 and 1-5. For linear mV and V ranges, connection is made to Terminals

4 and 5 (

1

16

-DIN controllers) or Terminals 3 and 2 (

1

4

-DIN &

1

8

-DIN controllers) in the

polarity shown in Figures 1-4 and 1-5. For details of the linear input ranges

available, refer to Appendix A.

1.3.6 Dual Setpoint Selection Input

With the Dual Setpoint option fitted, Terminals 11 and 12 (

1

16

-DIN controllers) or

Terminals 16 and 17 (

1

4

-DIN &

1

8

-DIN controllers) are used for external selection of

the active setpoint. These terminals may be connected to (a) the voltage-free

contacts of a switch or relay, or (b) a TTL-compatible voltage. Setpoint selection is

as follows:

Voltage-Free: Contacts open - Setpoint 1 selected

Contacts closed - Setpoint 2 selected

TTL-compatible: >2.0V - Setpoint 1 selected

<0.8V - Setpoint 2 selected

NOTE: The Dual Setpoint option and the RS485 Serial Communications

option are mutually exclusive.

1.3.7 Relay Outputs

The contacts are rated at 2A resistive at 120/240V AC.

1.3.8 SSR Drive Outputs

These outputs produce a time-proportioned non-isolated DC signal (0 - 4.2V

nominal into 1k

minimum).

1.3.9 Solid State Outputs

These outputs provide up to 1A AC drive with a longer lifetime than an

electromechanical relay. For further details, refer to Appendix A.

1.3.10 DC Outputs

See Appendix A.

O054-1 1-7