beautypg.com

Option selection – West Control Solutions N8100 User Manual

Page 59

background image

NOTES:

1.

If Output 2 is set to be a relay/SSR drive/solid state

output, it may be a control output (COOL) or an

alarm output; if it is set to be a DC output, it can only

be a control output (COOL).

2.

If Output 3 is set to be a relay/SSR drive/solid state

output, it can only be an alarm output; if it is set to

be a DC output, it can only be a recorder (i.e.

re-transmitted process variable or setpoint) output.

The maximum setting available for this code is 4888. For example, the code for a

thermocouple input, DC 4 - 20mA primary output (Output 1) and relay Output 3

would be 2701.

NOTE: It is essential that this code is changed promptly whenever there is a

change to the Controller’s hardware configuration (change of input/output

type, alarm/recorder output added/removed etc.). The Controller software

depends upon this code to ensure that the Controller operates correctly.

This code may be viewed as a Read Only display in Operator Mode (see Volume

1, Subsection 1.10).

3.3

OPTION SELECTION

This indicates the option fitted (Communications Option, Dual Setpoint Option no

option at all). It is accessed whilst the Hardware Definition Code is displayed (see

Figure 3-3).

S054-3

3-3

59125

Value

0

1

2

3

4

5

7

8

Input

RTD/

Linear

DC mV

Thermo-

couple

Linear

DC mA

Linear

DC V

Output

1

Relay

SSR

Drive

DC

0 - 10V

DC

0 - 20mA

DC

0 - 5V

DC

4 - 20mA

Solid

State

Output

2/3

Not

fitted

Relay

SSR

Drive

DC

0 - 10V

DC

0 - 2-mA

DC

0 - 5V

DC

4 - 20mA

Solid

State

Table 3-1 Hardware Definition Code - Input/Output Type Selection

This manual is related to the following products: