if the saturated output has not caused the process variable to be corrected by a

pre-determined amount V after a time T has elapsed, the Loop Alarm goes active.

Subsequently, the Loop Alarm facility repeatedly checks the process variable and

the control output(s). When the process variable starts to change value in the

correct sense or when the saturated output comes out of saturation, the Loop

Alarm is de-activated.

For PID control, the Loop Alarm Time T is always set to twice the value of the Reset

(Integral Time Constant) parameter. For On/Off control, the user-defined value of

the Loop Alarm Time Set Up parameter (see Subsection 2.2.28) is used.

The value of V is dependent upon the input type:

°

C ranges:

2

°

C or 2.0

°

C

°

F ranges:

3

°

F or 3.0

°

F

Linear ranges:

10 least significant display units

For single output Controllers, the saturation limits are 0% and Out1Max%. For dual

output Controllers, the saturation limits are –100% and Out1Max%.

NOTES

1. Correct operation of the Loop Alarm depends upon reasonably

accurate PID tuning.

2. The Loop Alarm is automatically disabled during Manual Control Mode

and during execution of the Pre-Tune facility. Upon exit from Manual

Control Mode or after completion of the Pre-Tune routine, the Loop Alarm is

automatically re-enabled.

2.2.28

Loop Alarm Time

When full ON/OFF control is selected (i.e. Proportional Band 1 is set to 0) and Loop

Alarm is enabled, this parameter determines the duration of the saturation

condition after which the Loop Alarm will be activated. This parameter is omitted

from the Set Up display sequence if ON/OFF control is not selected or Loop Alarm

is disabled.

2.2.29

Scale Range Decimal

Point

This parameter, applicable only if a linear

input is fitted, defines the position of the

decimal point in values of the process

variable, setpoint, alarm levels and

recorder outputs as shown on the right.

2-11

O054-2

59125

Value

Decimal Point Position

0

xxxx

1

xxx.x

2

xx.xx

3

x.xxx