Communications baud rate, Communications address, Cold junction compensation enable/disable – West Control Solutions N8100 User Manual
Page 64: Lock code, Alarm hysteresis outputs
3.5
ALARM HYSTERESIS OUTPUTS
An alarm hysteresis output is active only when both alarms are active; it becomes
subsequently inactive only when both alarms become inactive. Thus, the status of
the Alarm Hysteresis output when one alarm is active and the other is inactive
depends upon the alarm status immediately prior to that alarm being activated;
thus, with two process high alarms:
3-8
S054-3
59125
Parameter
Identifier
Description
Comms. Baud
Rate
Selectable: 1200, 2400, 4800, 9600 Baud
Comms. Address
Unique address assigned to the controller;
in the range 1 - 32.
Cold Junction
Compensation
Enable/Disable*
Enabled (default)
Disabled
Lock Code
Read Only display of current four-digit Set Up
Mode Lock Code.