background image

1.3.11

RS485 Serial Communications Link

The cable used should be suitable for data transfer at the selected rate (1200,

2400, 4800 or 9600 Baud) over the required distance. Transmitters/receivers

conform to the recommendations in the EIA Standard RS485.

The “A” terminal on the Controller should be connected to the “A” terminal on the

master device; the “B” terminal on the Controller should be connected to the “B”

terminal on the master device. Where several Controllers are connected to one

master port, the master port transceiver in the active state should be capable of

driving a load of 12k

per Controller; the master port transceiver in the passive

state must have pull-up/pull-down resistors of sufficiently low impedance to ensure

that it remains in the quiescent state whilst supplying up to

±

100

µ

A each to the

Controller transceivers in the high impedance state.

NOTE: The RS485 Serial Communications option and the Dual

Setpoint option are mutually exclusive.

1-8

O054-1