Tuning parameters, Rate (derivative time constant), Reset (integral time constant) – West Control Solutions N8100 User Manual
Page 34: Manual reset (bias), On/off differential, Proportional band 1 value, Proportional band 2 value

3.3.5
Tuning Parameters
3-8
O054-3
59125
Parameter
Identifier
Description
Rate (Derivative
Time Constant)
D
May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. Defines the
derivative time constant for the control algorithm.
{DATA} is of the form mm.ss where mm = minutes
and ss = seconds. The decimal point position must
specify two decimal places, otherwise modification
will not occur.
Reset (Integral
Time Constant)
I
May be read/modified using aType 2 message or a
Type 3/Type 4 message sequence. Defines the
integral time constant for the control algorithm.
{DATA} is of the form mm.ss where mm = minutes
and ss = seconds. The decimal point position must
specify two decimal places, otherwise modification
will not occur.
1
Manual Reset
(Bias)
J
May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. Decimal point
position is as for input range.
ON/OFF
Differential
F
May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. Defines the
switching hysteresis for controllers with an ON/OFF
control output. Decimal point position = 1.
Overlap
/Deadband
K
May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. May be set to a
positive (overlap) or negative (deadband) value.
Decimal point position = 0.
2
Proportional
Band 1 value
P
May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. May be set to
0.0 (ON/OFF control) or within the range 0.5% -
999.9% of Output 1 power range. Decimal point
position = 1.
Proportional
Band 2 value
U
May be read/modified using a Type 2 message or a
Type 3/Type 4 message sequence. May be set to
0.0 (ON/OFF control) or within the range 0.5% -
999.9% of Output 2 power range. Decimal point
position = 1.
2