Parameter Identifier

Description

Output

3

Usage

Alarm 1 hardware output, direct-acting. Avail-

able only if relay/SSR drive/solid state output.
Alarm 1 hardware output, reverse-acting. Avail-

able only if relay, SSR drive or solid state output.
Direct-acting output for Logical OR of Alarm 1

and Alarm 2. Available only if relay, SSR drive,

or solid state output.
Reverse-acting output for Logical OR of Alarm 1

and Alarm 2. Available only if relay, SSR drive,

or solid state output.
Direct-acting output for Logical AND of Alarm 1

and Alarm 2. Available only if relay, SSR drive,

or solid state output.
Reverse-acting output for Logical AND of Alarm

1 and Alarm 2. Available only if relay, SSR drive,

or solid state output.
Loop Alarm output, direct-acting. Available only

if relay, SSR drive or solid state output.
Loop Alarm output, reverse-acting. Available

only if relay, SSR drive or solid state output.
Alarm Hysteresis output, direct-acting. Available

only if relay, SSR drive or solid state output.
Alarm Hysteresis output, reverse-acting.

Available only if relay, SSR drive or solid state

output.
Recorder Output - Setpoint (DC output only)

Recorder Output - Process Variable

(DC Output only)

Direct-acting

Reverse-acting

AL1 OFF, AL2 OFF: Relay de-energised AL1 OFF, AL2 OFF: Relay energised
AL1 ON, AL2 OFF: Relay de-energised AL1 ON, AL2 OFF: Relay energised
AL1 OFF, AL2 ON: Relay de-energised AL1 OFF, AL2 ON: Relay energised
AL1 ON, AL2 ON:

Relay energised

AL1 ON, AL2 ON:

Relay de-energised

Example of Logical Combination of Alarms - Logical AND of Alarm 1 & Alarm 2