Operation, 7 conctb (concentration transducer block) – KROHNE MFC 400 FOUNDATION FIELDBUS User Manual
Page 50
4
OPERATION
50
MFC 400
www.krohne.com
11/2013 - 4003221901 - AD MFC 400 FF R01 en
4.7 CONCTB (Concentration Transducer Block)
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value
ALERT_KEY
ALERT_KEY
ALERT_KEY
ALERT_KEY
Alert Key
R/W
The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
0
Setting:
1...255
BLOCK_ERR
BLOCK_ERR
BLOCK_ERR
BLOCK_ERR
Block Error
R
This parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
Other
Setting:
•
Other: Non-specific error active
•
Block Configuration: Error detected in block configuration
•
Link Configuration: Error detected in link configuration
•
Simulation Active: Simulation enabled in this block
•
Local Override: Output tracking of faultstate active
•
Device Fault State: Device faultstate set
•
Device Maintenance: Device needs maintenance soon
•
Input Failure: Process variable has bad status
•
Output Failure: Failure detected in output hardware
•
Memory Failure: Memory error detected
•
Lost Static Data: Static parameters cannot be recovered
•
Lost NV Data: Non-volatile parameters cannot be recovered
•
Readback Check: Failure detected in READBACK
•
Maintenance Needed: Device NEEDS maintenance NOW
•
Power Up: Recovery from power failure
•
Out Of Service: Block actual mode is out of service
MODE_BLK
MODE_BLK
MODE_BLK
MODE_BLK
Block Mode
The actual, target, permitted and normal modes of the block.
-
TARGET
Target
R/W
This is the mode requested by the operator. Only one mode
from those allowed by the permitted mode parameter may be
requested.
Auto
Setting:
Auto / OOS
ACTUAL
Actual
R
This is the current mode of the block, which may differ from
the target based on operating conditions. Its value is
calculated as part of block execution.
Auto
Setting:
Auto / OOS
PERMITTED
Permitted
R/W
Defines the modes which are allowed for an instance of the
block. The permitted mode is configured based on application
requirement.
Auto
OOS
Setting:
Auto / OOS
NORMAL
Normal
R/W
This is the mode which the block should be set to during
normal operating conditions.
Auto
Setting:
Auto / OOS
ST_Rev
ST_Rev
ST_Rev
ST_Rev
Static Revision
R
The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
0
Setting:
0...65535