Operation – KROHNE MFC 400 FOUNDATION FIELDBUS User Manual
Page 26
4
OPERATION
26
MFC 400
www.krohne.com
11/2013 - 4003221901 - AD MFC 400 FF R01 en
(1)(12)(31):Check process for entrained gas. / (1)(13)(31):
Check process cond. In case of remote sensor check cabling. /
(1)(14)(28):Check cable and connection at terminal B, reduce
load. / (1)(14)(29):Check cable and connection at terminal B,
reduce load. / (1)(14)(30):Check cable and connection at
terminal A, reduce load. / (1)(14)(31):Check cable and
connection at terminal A, reduce load. / (1)(15)(30):Check
device connected to current input B. / (1)(15)(31):Check device
connected to current input A. / (1)(16)(00):reserved /
(1)(17)(30):Save settings to Backup 2. / (1)(17)(31):Save
settings to Backup 1. / (1)(18)(29):Change one param. The
status should disappear within 1 minute. / (1)(18)(30):Please
contact the factory. / (1)(18)(31):Check if converter is correctly
mounted and fixed into housing. / (1)(19)(00):reserved /
(1)(20(27):Check process conditions or pipe diameter setting. /
(1)(20)28):Check process conditions and density calibration. /
(1)(20)(30):Check process conditions. / (1)(20)(31):Check
process conditions. / (1)(21)(03):Check the range settings of
the related output. / (1)(21)(04):Check the range settings of the
related output. / (1)(21)(05):Check the range settings of the
related output. / (1)(21)(06):Check the range settings of the
related output. / (1)(21)(07):Check the range settings of the
related output. / (1)(21)(09):Check the range settings of the
related output. / (1)(22)(26):Check reason for electronics over
temperature. / (1)(23)(31):Check cabling in case of remote
device or replace sensor. / (1)(24)(00):reserved /
(1)(25)(07):Turn off simulation / (1)(25)(08):Turn off
simulation / (1)(25)(09):Turn off simulation / (1)(25)(10):Turn
off simulation / (1)(25)(11):Turn off simulation /
(1)(25)(12):Turn off simulation / (1)(25)(22): Check Fieldbus
Configuration. / (1)(25)(28): No Action Required. / (1)(25)(29):
Turn off simulation mode / (1)(25)(30):For normal operation
turn off simulation mode. / (1)(25)(31):For normal operation
turn off simulation mode. / (1)(26)(00):reserved /
(1)(27)(00):reserved / (1)(28)(00):reserved / (1)(29)(02):Check
IO B configuration or reset to factory configuration. /
(1)(29)(03):Check IO B configuration or reset to factory
configuration. / (1)(29)(04):Check IO A configuration or reset to
factory configuration. / (1)(29)(05):Check IO A configuration or
reset to factory configuration. / (1)(29)(10):Check IO2
configuration or reset to factory configuration. /
(1)(29)(11):Check IO1 configuration or reset to factory
configuration. / (1)(29)(12):Check display configuration or
reset to factory configuration. / (1)(29)(21): Check fieldbus
configuration or reset to factory configuration. / (1)(29)(25):
Check config. of the related function. Reset config. to factory. /
(1)(29)(26):Check config. of the related function. Reset config.
to factory. / (1)(29)(30):Check config. of the related function.
Reset config. to factory. / (1)(29)(31):Check config. of the
related function. Reset config. to factory. / (1)(30)(01):Perform
power reset. If the status returns, contact the factory. /
(1)(30)(02):Perform power reset. If the status returns, contact
the factory. / (1)(30)(07):Perform power reset. If the status
returns, contact the factory. / (1)(30)(08):Perform power reset.
If the status returns, contact the factory. / (1)(30)(16):Perform
power reset. If the status returns, contact the factory. /
(1)(30)(21):Perform power reset. If the status returns, contact
the factory. / (1)(30)(26):Perform power reset. If the status
returns, contact the factory. / (1)(30)(27):Perform power reset.
If the status returns, contact the factory. / (1)(30)(28):Perform
power reset. If the status returns, contact the factory. /
(1)(30)(31):Perform power reset. If the status returns, contact
the factory. / (1)(31)(30): Check cabling in case of remote
device or replace sensor. / (1)(31)(31):Replace sensor
FD_SIMULATE
FD_SIMULATE
FD_SIMULATE
FD_SIMULATE
Field Diagnostic
Simulate
Used as the field diagnostic condition when the simulation is
enabled.
-
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value