Operation – KROHNE MFC 400 FOUNDATION FIELDBUS User Manual

Page 39

background image

OPERATION

4

39

MFC 400

www.krohne.com

11/2013 - 4003221901 - AD MFC 400 FF R01 en

EU_0

EU at 0%

R/W

The engineering unit value which represents the lower end of

range of the associated block parameter.

0.0

UNITS_INDEX

Units Index

R/W

Device Description units code index for the engineering unit

descriptor for the associated block value.

Uninitialized

Setting:

All units are possible.

DECIMAL

Decimal

R/W

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

0

PV

PV

PV

PV

Process Value

Either the primary analogue value for use in executing the

function or a process value associated with it.

-

Status

R

Digital transducers, unlike their analogue versions, can detect

faults that make the measurement bad or prevent the

actuator from responding. This additional, valuable

information will be passed along with each transmission of a

data value in the form of a status attribute.

0

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

PV_FTIME

PV_FTIME

PV_FTIME

PV_FTIME

PV F Time

(Process Value

Filter Time)

R/W

Time constant of a single exponential filter for the PV, in

seconds.

0

Setting:

0.0…60.0

SIMULATE

SIMULATE

SIMULATE

SIMULATE

Simulate

Mix

Allows the transducer analogue input or output to the block to

be manually supplied when "Simulate" is enabled. When

simulation is disabled, the simulate value and status track the

actual value and status.

-

Simulate Status

R/W

Used for the transducer status when simulation is enabled.

0

Simulate Value

R/W

Used for the transducer value when simulation is enabled.

0.0

Setting:

-3.39 E38 … +3.39 E38, - INF, + INF

Transducer Status

R

Status of value supplied by transducer.

0

Transducer Value

R

Current value supplied by transducer.

0.0

Simulate

En/Disable

R/W

The parameter "SW_Simulated" in RB Block must be enabled. Disabled

Setting:

Uninitialized / Disabled / Active

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

STATUS_OPTS

Status Option

R/W

Options which the user may select in the block processing of

status.

Uninitialized

Setting:

Propagate Fault Forward / Uncertain if limited / BAD if

limited / Uncertain if Man.

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

UPDATE_EVT

Update Event

This alert is generated by any change to the static data.

-

Unacknowledged

RW

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

Update State

R

A discrete enumeration which gives an indication of whether

the alert has been reported.

Uninitialized

Setting:

Uninitialized / Reported / Not Reported

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value