OPERATION

28

MFC 400

www.krohne.com

11/2013 - 4003221901 - AD MFC 400 FF R01 en

GRANT

Grant

R/W

Depending on the philosophy of the plant, the operator or a

higher level device (HLD) or a local operator's panel (LOP) in

the case of "Local", may turn on an item of the "Grant"

attribute - "Program, Tune, Alarm or Local".

Uninitialized

Setting:

Program / Tune / Alarm / Local / Operate

DENY

Deny

R/W

The Denied attribute is limited for use by a monitoring

application in an interface device and may not be changed by

an operator.

Uninitialized

Setting:

Program denied / Tune denied / Alarm denied / Local denied /

Operate denied

HARD_TYPES

HARD_TYPES

HARD_TYPES

HARD_TYPES

Hardware Types

R

The types of hardware available as channel numbers.

Scalar input

ITK_VER

ITK_VER

ITK_VER

ITK_VER

ITK Version

(Interoperatibility Test

Kit)

R

Major revision number of the interoperability test case used to

register this device.

6

LIM_NOTIFY

LIM_NOTIFY

LIM_NOTIFY

LIM_NOTIFY

Limit Notify

R/W

Maximum number of unconfirmed alert notify messages

allowed.

20

Setting:

0...255

MANUFAC_ID

MANUFAC_ID

MANUFAC_ID

MANUFAC_ID

Manufacturer ID

R

Manufacturer identification number - used by an interface

device to locate the DD file for the resource.

KROHNE

Setting:

KROHNE

MAX_NOTIFY

MAX_NOTIFY

MAX_NOTIFY

MAX_NOTIFY

Maximum Notify

R

Maximum number of unconfirmed alert notify messages

possible.

20

Setting:

0...255

MEMORY_SIZE

MEMORY_SIZE

MEMORY_SIZE

MEMORY_SIZE

Memory Size

R

Available configuration memory in the empty resource. To be

checked before attempting a download.

0

MIN_CYCLE_T

MIN_CYCLE_T

MIN_CYCLE_T

MIN_CYCLE_T

Minimium Cycle Time

R

Time duration of the shortest cycle interval of which the

resource is capable (in [1/32 ms]).

6400

NV_CYCLE_T

NV_CYCLE_T

NV_CYCLE_T

NV_CYCLE_T

Nonvolatile Cycle

Time

R

Interval between writing copies of NV parameters to non-

volatile memory. Zero means never (in [1/32 ms]).

256000

RESTART

RESTART

RESTART

RESTART

Restart

R/W

Allows a manual restart to be initiated. Several degrees of

restart are possible. They are 1: Run, 2: Restart resource, 3:

Restart with defaults and 4: Restart processor.

Run

Setting:

Uninitialized / Run / Resource / Defaults / Processor

RS_STATE

RS_STATE

RS_STATE

RS_STATE

Resource State

R

State of the function block application state machine.

Standby

Setting:

Uninitialized / Start_Restart / Initialization / Online Linking /

Online / Standby / Failure

SET_FSTATE

SET_FSTATE

SET_FSTATE

SET_FSTATE

Set Fault State

R/W

Allows the fault state condition to be manually initiated by

selecting "Set".

Off

Setting:

Off

SHED_RCAS

SHED_RCAS

SHED_RCAS

SHED_RCAS

Shed Remote Cascade

R/W

Time duration at which to give up on computer writes to

function block RCAS locations.

640000

Setting:

0...4294967295 in [1/32 ms]

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value