CHANNEL
CHANNEL
CHANNEL
CHANNEL
Channel
R/W
The number of the logical hardware channel that is connected
to this I/O block. This information defines the transducer to be
used going to or from the physical world.
Note:
Note:
Note:
Note:
W = Writeable only by setting "OOS" in MODE_BLK
Uninitialized
Setting:
0: Uninitialized
1: Mass Flow
2: Density
3: Temperature
4: Flow Velocity
5: Volume Flow
21: Concentration 1
22: Concentration 2
23: Concentr. MassFlow 1
24: Concentr. MassFlow 2
25: Concentr. Vol.Flow 1
26: Concentr. Vol.Flow 2
41: Drive Level
42: Sensor Average
43: Sensor Deviation
44: 2 Phase Signal
45: Tube Frequency
46: Strain 1
47: Strain 2
48: Electronic Temperature
FIELD_VAL
FIELD_VAL
FIELD_VAL
FIELD_VAL
Field Value
R
Raw value of the field device in percent of the PV range, with a
status reflecting the transducer condition, before signal
characterization (L_TYPE) or filtering (PV_FTIME).
-
Status
R
Digital transducers, unlike their analogue versions, can detect
faults that make the measurement bad or prevent the
actuator from responding. This additional, valuable
information will be passed along with each transmission of a
data value in the form of a status attribute.
Bad
Non Specific
Not Limited
Value
R
A numerical quantity entered by a user or calculated by the
algorithm.
0.0
GRANT_DENY
GRANT_DENY
GRANT_DENY
GRANT_DENY
Grant Deny
Options for controlling access of host computers and local
control panels to operating, tuning and alarm parameters of
the block.
-
GRANT
Grant
R/W
Depending on the philosophy of the plant, the operator or a
higher level device (HLD) or a local operator's panel (LOP) in
the case of "Local", may turn on an item of the "Grant"
attribute - "Program, Tune, Alarm or Local".
Uninitialized
Setting:
Program / Tune / Alarm / Local / Operate
DENY
Deny
R/W
The deny attribute is provided for use by a monitoring
application in an interface device and may not be changed by
an operator.
Uninitialized
Setting:
Program denied / Tune denied / Alarm denied / Local denied /
Operate denied
HI_ALM
HI_ALM
HI_ALM
HI_ALM
High Alarm
The status for High Alarm and its associated time stamp.
Settings of 5 subelements see in the following part.
-
HI_HI_ALM
HI_HI_ALM
HI_HI_ALM
HI_HI_ALM
High High Alarm
Mix
The status for High High Alarm and its associated time stamp.
Settings of 5 subelements see in the following part.
-
Settings of 5 subelements for previous 2 parameters High Alarm and High High Alarm:
Unacknowledged
R/W
Setting:
Uninitialized / Acknowledged / Unacknowledged
Uninitialized
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value