TRANSDUCER_

TRANSDUCER_

TRANSDUCER_

TRANSDUCER_

TYPE_VER

TYPE_VER

TYPE_VER

TYPE_VER

Transducer Type

Version

R

Identifies the version of the transducer that follows. Format is

XXYY where XX is the major spec revision and YY is the

manufacturer revision.

0x0101

TUBE_DIAMETER_

TUBE_DIAMETER_

TUBE_DIAMETER_

TUBE_DIAMETER_

CONSTANT

CONSTANT

CONSTANT

CONSTANT

Pipe Diameter

R/W

Pipe diameter used to calculate flow velocity (Fct. C1.1.3).

10.0 mm

Settings:

1.00..500.00 mm

XD_ERROR

XD_ERROR

XD_ERROR

XD_ERROR

Transducer Error

R

One of the transducer error codes defined in the FF

Transducer Specifications in section "4.7 Block Alarm

Subcodes".

Uninitialized

Settings:

16: Unspecified error

17: General error

18: Calibration error

19: Configuration error

20: Electronics Failure

21: Mechanical Failure

22: I/O Failure

23: Data Integrity Error

24: Software Error

25: Algorithm Error

ZERO_ADD_

ZERO_ADD_

ZERO_ADD_

ZERO_ADD_

OFFSET

OFFSET

OFFSET

OFFSET

Zero Add. Offset

R/W

Manual setting of additional zero offset (Fct. C1.1.2).

0.0 kg/h

Settings:

-115200.0…1115200.0 kg/h

Parameter

Parameter

Parameter

Parameter
DD name

Access

Description and settings

Initial Value