Operation – KROHNE MFC 400 FOUNDATION FIELDBUS User Manual
Page 49
OPERATION
4
49
MFC 400
www.krohne.com
11/2013 - 4003221901 - AD MFC 400 FF R01 en
TRANSDUCER_
TRANSDUCER_
TRANSDUCER_
TRANSDUCER_
TYPE_VER
TYPE_VER
TYPE_VER
TYPE_VER
Transducer Type
Version
R
Identifies the version of the transducer that follows. Format is
XXYY where XX is the major spec revision and YY is the
manufacturer revision.
0x0101
TUBE_DIAMETER_
TUBE_DIAMETER_
TUBE_DIAMETER_
TUBE_DIAMETER_
CONSTANT
CONSTANT
CONSTANT
CONSTANT
Pipe Diameter
R/W
Pipe diameter used to calculate flow velocity (Fct. C1.1.3).
10.0 mm
Settings:
1.00..500.00 mm
XD_ERROR
XD_ERROR
XD_ERROR
XD_ERROR
Transducer Error
R
One of the transducer error codes defined in the FF
Transducer Specifications in section "4.7 Block Alarm
Subcodes".
Uninitialized
Settings:
•
16: Unspecified error
•
17: General error
•
18: Calibration error
•
19: Configuration error
•
20: Electronics Failure
•
21: Mechanical Failure
•
22: I/O Failure
•
23: Data Integrity Error
•
24: Software Error
•
25: Algorithm Error
ZERO_ADD_
ZERO_ADD_
ZERO_ADD_
ZERO_ADD_
OFFSET
OFFSET
OFFSET
OFFSET
Zero Add. Offset
R/W
Manual setting of additional zero offset (Fct. C1.1.2).
0.0 kg/h
Settings:
-115200.0…1115200.0 kg/h
Parameter
Parameter
Parameter
Parameter
DD name
Access
Description and settings
Initial Value