beautypg.com

Operation, 3 linearisation, 4 distance measurement – KROHNE OPTIWAVE 7300C EN User Manual

Page 69

background image

OPERATION

6

69

OPTIWAVE 7300 C

www.krohne.com

03/2014 - 4000172405 - HB OPTIWAVE 7300 R07 en

How to change from point-to-point to multidrop mode

• Enter supervisor mode.
• Go to Advanced Setup > Output 1 (HART) > HART Address

Advanced Setup > Output 1 (HART) > HART Address

Advanced Setup > Output 1 (HART) > HART Address

Advanced Setup > Output 1 (HART) > HART Address.

• Enter a value between 1 and 15 and push [^

^

^

^] to confirm (see the caution below).

• Push the Escape buttons ([>>>>] + [

]) until you get the save/cancel screen.

• Select save.
• Push [^

^

^

^].

i

Output 1 switches to multidrop mode. The current output is set to 4 mA. This value does not
change in multidrop mode.

How to change from multidrop to point-to-point mode

• Enter supervisor mode.
• Go to Advanced Setup > Output 1 (HART) > HART Address

Advanced Setup > Output 1 (HART) > HART Address

Advanced Setup > Output 1 (HART) > HART Address

Advanced Setup > Output 1 (HART) > HART Address.

• Enter the value 0000 and then push [^

^

^

^] to confirm.

• Push the Escape buttons ([>>>>] + [

]) until you get the save/cancel screen.

• Select save.
• Push [^

^

^

^].

i

Output 1 switches to point-to-point mode. The current output changes to a range of
4...20 mA or 3.8...20.5 mA (this range is specified in Advanced Setup > Output 1 (HART) >

Advanced Setup > Output 1 (HART) >

Advanced Setup > Output 1 (HART) >

Advanced Setup > Output 1 (HART) >

Output Range

Output Range

Output Range

Output Range).

6.4.3 Linearisation

You can use the Linearisation Table

Linearisation Table

Linearisation Table

Linearisation Table (menu item C.1.22) to make sure that readings are

consistently accurate.

• Go to Supervisor > Advanced Setup > Installation Setup > Linearisation Table

Supervisor > Advanced Setup > Installation Setup > Linearisation Table

Supervisor > Advanced Setup > Installation Setup > Linearisation Table

Supervisor > Advanced Setup > Installation Setup > Linearisation Table.

• Type in the number of reference points (up to 50 points). Push [^

^

^

^].

i

This shows the linearisation table with default values.

• Push [>>>>] to type in new data. The device reading is given on the second line Device distance

Device distance

Device distance

Device distance.

• Fill the tank to any given level.
• Make an appropriate reference measurement. Type this data on the line Real distance

Real distance

Real distance

Real distance.

• Repeat these steps until all the cells in the linearisation table are completed.
• Push [^

^

^

^].

• Push [>>>>] and [

] (Esc) at the same time to exit to the "save settings" window.

• Select Save

Save

Save

Save and push [^

^

^

^].

i

The device will go back to operator mode.

6.4.4 Distance measurement

The device displays distance measurements when an output is set to distance.

Menu items related to distance measurement are:

• Output Function (C.3.1 or C.4.1)
• Tank Height (C.1.2)

CAUTION!
Make sure that the address for this device is different from others in the multidrop network.