OPERATION

64

OPTIWAVE 7300 C

www.krohne.com

03/2014 - 4000172405 - HB OPTIWAVE 7300 R07 en

C.1.8

Overfill

Detection

If this function is switched on, the

device will monitor the level even if it is

in the blocking distance. The displayed

output stays fixed at the blocking

distance, but an error message will

warn the user that the tank is

overfilling.

Yes, No

No

C.1.9

Blocking

Distance

The distance from the flange to the top

limit of the measuring range (a zone

given by the user where it is not

possible to measure). We recommend

a blocking distance at least 100 mm /

4¨ below the antenna. If the distance is

less than the blocking distance, the

device continues to display the

blocking distance.

min-max:

antenna extension (C.1.6) +

50 mm / 2¨…tank height (C.1.2)

0.5 m / 1.6 ft

C.1.10

Reference

Offset

Offset relating to a reference location

(distance). This value is positive when

the reference location is above the

device flange face and negative if

below. For more data, refer to

Distance

measurement

on page 69.

min-max:

-tank height…50 m /

-tank height...164.05 ft

0 m / 0 ft

C.1.11

Tank Bottom

Offset

Offset relating to a reference location

(level). The device reference point for

this parameter is the bottom of the

tank (set in menu item C.1.2.0). This

value is positive when the reference

location is below the tank bottom and

negative if above. For more data, refer

to

Level measurement

on page 70.

min-max:

-tank height...3000 m /

-tank height...9843 ft

0 m / 0 ft

C.1.12

Time Constant

Using this function, the device

processes several measurement

readings to filter out disturbances.

Increasing the time constant will

smoothen the integrated readings,

decreasing will roughen the readings.

min-max: 1...100 sec (seconds)

3 sec

C.1.13

Measuring

Mode

The device uses the dielectric constant

r

) of the tank contents to monitor

level. This menu item is set by default

to "Direct Measuring" for tank contents

with an ε

r

>1.6. If ε

r

is low, select "TBF

Partial" mode. If ε

r

is very low (<1.5),

select "TBF Full". If you want the

device to measure level using the first

good radar signal it finds, select

"Option 1". If you want the device to

measure level but ignore all the radar

signals stored in the empty spectrum

scan, select "Option 2". "Option 3" is

not yet available.

Direct Measuring, TBF Partial,

TBF Full, Option 1, Option 2,

Option 3

Direct

Measuring

C.1.14

Product Er

The device automatically calculates the

level based on the product ε

r

. If you

select "TBF Partial" or "TBF Full" in

item C.1.13, you can change this value

manually to adjust readings.

min-max: 1.01…99.90

4

C.1.15

Tracing

Velocity

This function sets the maximum rate of

change of level. The measured value

cannot change faster than the tracing

velocity.

min-max:

0.001…10.000 m/min /

0.003…32.8 ft/min

0.5 m/min /

1.64 ft/min

Menu

No.

Function

Function description

Selection list