6.3.5 Function description
A. Quick setup
Menu
No.
Step
Function
Function description
Selection list
Default
A.1 Setup Mode
A.1.1
A.1.1
A.1.1
A.1.1
Complete
Complete
Complete
Complete
This follows the steps given in
This follows the steps given in
This follows the steps given in
This follows the steps given in
the Installation, Empty
the Installation, Empty
the Installation, Empty
the Installation, Empty
Spectrum, Conversion and
Spectrum, Conversion and
Spectrum, Conversion and
Spectrum, Conversion and
Outputs setup modes.
Outputs setup modes.
Outputs setup modes.
Outputs setup modes.
A.1.2
A.1.2
A.1.2
A.1.2
Installation
Installation
Installation
Installation
Follow this procedure to
Follow this procedure to
Follow this procedure to
Follow this procedure to
describe the tank and the
describe the tank and the
describe the tank and the
describe the tank and the
product.
product.
product.
product.
1
Installation Type
The tank material.
Metal Tank, Plastic Tank,
Free Air Application
Metal Tank
2
Tank Height /
Measuring Range
"Tank Height" is the distance
from the tank connecting
flange face/thread stop to the
tank bottom. "Measuring
Range" (for "Free Air
Application" only) is the
maximum distance that the
device must measure.
min-max:
0.20…80 m / 0.66…262 ft
20 m
3A
Application Type
The conditions in which the
device is used. If the surface of
the product is flat, select
"Storage". If the surface of the
product is disturbed, select
"Process". If the surface of the
product is agitated with
vortexes and foam, select
"Agitator". If the device is
installed in a still well, select
"...+Stillwell".
Process, Storage, Agitator,
Process+Stillwell,
Storage+Stillwell,
Agitator+Stillwell
Process or
Process
+Stillwell
The conditions in which the
device is used. For free air
applications only. If the surface
of the product is flat, select
"No Disturbance". If the
surface of the product is
disturbed, select "Medium
Disturbance". If there are
bubbles on the surface of the
product and also vortexes and
foam, select "Heavy
Disturbance".
No Disturbance, Medium
Disturbance, Heavy
Disturbance
No Disturb-
ance
4A
Stillwell Diameter
The inner diameter of the
stillwell. Step 4 is available if
you set "...+Stillwell" in step 3.
min-max:
8…200 mm / 0.31…7.88¨
100 mm /
3.94¨
4B
Stillwell Height
The height of the stillwell. Step
4 is available if you set
"...+Stillwell" in step 3.
min-max:
0…80 m / 0…262 ft
10 m /
32.81 ft
5
Blocking Distance
A zone given by the user where
it is not possible to measure.
We recommend a blocking
distance at least 100 mm / 4¨
below the antenna.
min-max:
antenna extension (C.1.6) +
50 mm / 2¨…tank height
(C.1.2)
1
2
6
Settings summary
7
Current changes
must be saved or
cancelled before
proceeding
Save, Cancel
3