6

OPERATION

60

OPTIWAVE 7300 C

www.krohne.com

03/2014 - 4000172405 - HB OPTIWAVE 7300 R07 en

...

Current changes

must be saved or

cancelled before

proceeding

Save, Cancel

3

Save

A.1.5

A.1.5

A.1.5

A.1.5

Outputs

Outputs

Outputs

Outputs

Follow this procedure to

Follow this procedure to

Follow this procedure to

Follow this procedure to

describe the output

describe the output

describe the output

describe the output

characteristics.

characteristics.

characteristics.

characteristics.

1

Output 1: Output

Function

Select an output function to

scale the current values

(output 1). This is not displayed

in the operator mode.

Level, Distance, Volume

(Mass), Ullage Volume

(Ullage Mass), Reflection

Level

2

Output 1 (HART):

4 mA

This assigns a measurement

value to 4 mA (output 1).

min-max:

0…20 m / 0…65.62 ft

0 m / 0 ft

3

Output 1 (HART):

20 mA

This assigns a measurement

value to 20 mA (output 1).

min-max:

0…90 m / 0…295.29 ft

Depends on

the output

function

4

Output Range

This sets the effective range of

output 1 with or without over-

run.

3.8…20.5 mA (NAMUR),

4…20 mA

4…20 mA

5

Error Handling

This sets the behaviour of

current output 1 if an error

occurs. Hold

Hold

Hold

Hold means that the

output current stays at the

value where the error

occurred. Hold

Hold

Hold

Hold is not available

if 3.8…20.5 mA (NAMUR) is the

output range.

3.6 mA, 22 mA, Hold

(4...20 mA range only)

22 mA

6

Output 1 (HART):

HART Address

Any HART

®

address greater

than 0 will activate HART

®

multidrop mode. Current

output stays constant at 4 mA.

min-max: 0…15

0

7

Output Function 2

4

Select an output function to

scale the current values

(output 2). This is not displayed

in the operator mode.

Level, Distance, Volume

(Mass), Ullage Volume

(Ullage Mass), Reflection

Level

8

Output 2 (Passive):

4 mA

4

This assigns a measurement

value to 4 mA (output 2).

min-max:

0…20 m / 0…65.62 ft

0 m / 0 ft

9

Output 2 (Passive):

20 mA

4

This assigns a measurement

value to 20 mA (output 2).

min-max:

0…90 m / 0…295.29 ft

Depends on

the output

function

10

OP2 Output Range

4

This sets the effective range of

output 2 with or without over-

run.

3.8…20.5 mA (NAMUR),

4…20 mA

4…20 mA

11

OP2 Error

Handling

4

This sets the behaviour of

current output 2 if an error

occurs. Hold means that the

output current stays at the

value where the error

occurred. Hold is not available

if 3.8…20.5 mA (NAMUR) is the

output range.

3.6 mA, 22 mA, Hold

(4...20 mA range only)

22 mA

12

Settings summary

Read only

Current changes

must be saved or

cancelled before

proceeding

Save, Cancel

Save

Menu
No.

Step

Function

Function description

Selection list

Default