2-5
TABLE 2-6. REAR OUTPUT TERMINAL STRIP TB1 TERMINAL ASSIGNMENTS
TERMINAL
SIGNAL NAME
FUNCTION
1
+S
Positive sense connection
2
+ OUT
Positive d-c output connection
3
GND NET
Grounding network connection
4
GND
Ground (chassis) connection
5
– OUT
Negative d-c output connection
6
–S
Negative sense connection
7
– OUT C
Connection to internal output capacitor
TABLE 2-7. VOLTAGE PROGRAMMING TERMINAL STRIP TB2, TERMINAL ASSIGNMENTS
TERMINAL
SIGNAL NAME
FUNCTION
1
–10V
–10V d-c reference voltage
2
V(NINV)
Noninverting input of uncommitted amplifier
3
SGND
Signal common
4
V(+IN)
Programming input for positive input signal
5
+10V
+10V d-c reference voltage
6
V(INV)
Inverting input of uncommitted amplifier
7
V(FBK)
Internal feedback resistor; the other end is connected to
uncommitted amplifier output
8
V(OUT)
Output of uncommitted amplifier
9
–V EXT
External analog programming voltage input: 0 to –10V pro-
grams 0 to 100% of EOmax.
10
SGND
Signal common
TABLE 2-8. CURRENT PROGRAMMING TERMINAL STRIP TB3, TERMINAL ASSIGNMENTS
TERMINAL
SIGNAL NAME
FUNCTION
1
–10V
–10V d-c reference voltage
2
C(NINV)
Noninverting input of uncommitted amplifier
3
SGND
Signal common
4
C(+IN)
Programming input for positive input signal
5
+10V
+10V d-c reference voltage
6
C(INV)
Inverting input of uncommitted amplifier
7
C(FBK)
Internal feedback resistor; the other end is connected to
uncommitted amplifier output
8
C(OUT)
Output of uncommitted amplifier
9
C EXT
External analog programming voltage input: 0 to –10V pro-
grams 0 to 100% of IOmax. Usually connected to output of
uncommitted amplifier.
10
SGND